WeCo - HeSU UNIVERSAL MODEL 5K3 UNIVERSAL STACKABLE
HeSU 5K3-R20 STACKABLE * HIGH CURRENT V_2.00_2019
Pag. 33
SINGLE CLUSTER CONFIGURATION 120A -CABLES
NO HUB IS REQUIRED FOR SINGLE CLUSTER
ATTENTION
Connect two 25 mm² AWG Wire of the same length on each terminal as shown above
Strictly respect the below chart for the cluster configuration with standard kit 25 mm cables
If more power/current is required must refer to the next paragraph
Single cable 25mm²
POSITIVE
Single cable 25mm²
NEGATIVE
MASTER BATTERY
SLAVE # 3
SLAVE # 2
SLAVE # 1
SLAVE # 4
CAN BUS
Communication Cable to
the inverter