Combustion air inlet and exhaust lines
Air Top 2000 S
58
Total bends:
Combustion air line: max. 270°
Exhaust line:
max. 270°
Only for ADR: The statutory regulation of ADR (Accord européen relatif
au transport international des marchandises dangereuses par route)
governing the routing of the exhaust line, part 9 para. 9.2.4.7, must be
adhered to.
Fig 22:
Exhaust pipe opening
Installation position
An attachment is required no further than 150 mm from the end of the
exhaust pipe to ensure that the angle of 90°
±
10° is achieved
Discharge direction almost vertical 90°
±
10°