background image

7

ELECTRICAL WIRING

The power burner is shipped completely wired.  It is only necessary to supply the 115 volt circuit, thermostat and limit circuit.

All wiring must conform with the National electric Code or the code legally authorized in the locality where the installation is
being made.  The burner, when installed, must be electrically grounded in accordance with local codes or, in the absence of
local codes, with the National Electrical Code, ANSI/NFPA No. 70-1987.  See wiring diagrams, Figures 12&13.

If an external electrical source is utilized, the conversion burner, when installed, must be electrically grounded in accordance

with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70-1987.

CAUTION: Label all wires prior to disconnection when servicing controls.  Wiring errors can cause improper and dangerous

operation.  Verify proper operation after servicing.

LIMIT CONTROL SWITCHES

Warm air furnaces (gravity and forced air) should be equipped with an automatic temperature limit control switch.  Hot water

boilers (forced or gravity) should be equipped with an automatic temperature limit control switch.  

Steam or vapor boilers be provided with means to guard against firing a dry boiler or one in which the water is dangerously low.

IMPORTANT:  On installations where an oil burner is being replaced with a gas burner, the controls on the boiler or furnace

will have to be checked for compatibility with the gas burner.  All controls should be checked to insure that they
operate properly and that they are in good condition.  In no case should any limit or safety control be bypassed
or wired in such a manner that it will result in unsafe operation of the burner or appliance.  If the controls on
the appliance are not compatible with the burner operation they should be replaced with the proper controls.

THERMOSTAT

The thermostat should be installed on an inside wall and should be located in the natural circulating path of room air.

Locations which would expose the thermostat to cold air, or drafts from windows, door, or openings leading to the outside, or to
air currents from cold or warm air registers, or where the natural circulation of air is shut off such as behind doors, above or
below mantels, shelves or in corners, should be avoided.  The thermostat should not be exposed to heat from nearby radiators,
lamps, rays of the sun or mounted on a wall near pipes, warm air ducts or chimney flue.  Any hole in the plaster or panel
through which the thermostat wires pass should be sealed to prevent drafts.

The maximum comfort to be obtained from any automatic heating installation is dependent to a great extent upon the proper

installation and adjustment of the room thermostat.

GAS PIPING

All piping must comply with local codes and ordinances or the National Fuel Gas Code ANSI Z223. 1-1984 and  NFPA No.

54.  A sediment trap or drip leg must be installed in the supply line to the burner.

A union shall be installed in the gas line adjacent to and upstream from the control manifold and downstream from the

manual main shutoff trap or drip leg must be installed in the supply line to the burner.

A 1/8” N.P.T. (3.175mm) plugged tapping accessible for test gauge connection shall be installed immediately upstream of the

gas supply connection for the purpose of determining the gas supply pressure to the burner.

A manual shutoff valve shall be installed in the gas supply line external to the appliance, see Figure 7.

The gas line should be a separate supply direct from the meter to the burner.  It is recommended that new pipe; be used and

located so that a minimum amount of work will be required in future servicing.  The piping should be so installed as to be
durable, substantial and gas tight.  It should be clear and free from cutting burrs and defects in structure or threading.  Cast iron
fittings or aluminum tubing should not be used for the main gas circuit.  Joint compounds (pipe dope) should be used sparingly
on male threads only and be approved for all gases.

It is recommended that Table 8 be used to determine the size pipe to use from the meter to the burner.

The building structure should not be weakened by installation for the gas piping.  The piping should not be supported by the

other piping, but should be firmly supported with pipe hooks, straps, bands or hangers.  Butt or lap welded pipe should not be
bent.

The gas piping should be so installed so as to prevent an accumulation of condensation and it must be protected against

freezing.  A horizontal pipe should be pitched so that it grades toward the meter and is free from sags.  The pipe should not be
run through or in an air duct or clothes chute.

The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure

testing of the system at test pressure in excess of 1/2 (3447 PaG) psig.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any

pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 (3447 PaG) psig.

TESTING PIPING FOR LEAKS

Before turning gas under pressure into piping, all openings from which gas can escape should be closed.  Immediately after

turning on gas, the system should be checked for leaks.  This can be done by watching the 1/2 cubic feet (.014m

3

) test dial and

allowing 5 minutes to show any movement, or by soaping each pipe connection and watching for bubbles.  If a leak is found,
make the necessary repairs and repeat the above test.

Defective pipes or fittings should be replaced and not repaired.  Never use a flame or fire in any form to locate gas leaks, use

a soap solution.

Содержание P265DI

Страница 1: ...store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical sw...

Страница 2: ...have been heated adequately without wide variations in temperature without objectionable drafts and without excessive fuel costs in the past If the heating system is deficient with respect to any of t...

Страница 3: ...plugs or any other condition which might make the unit unsatisfactory for gas conversion is found proper arrangements should be made for replacement or repair before proceeding with the burner install...

Страница 4: ...ssure point adjuster Insert in slot cut in flue pipe When adjustment is completed scribe a line on adjuster so it can be relocated Remove adjuster trim off excess slit remainder vertically and bend se...

Страница 5: ...152 4mm 180 000 52 75 250 000 73 27 7 inch 177 8mm NOTE If the flue pipe exceeds 10 ft 3 048m in length or contains more than two elbows use next size larger pipe and draft hood NO MOVEABLE FLUE PIPE...

Страница 6: ...er was designed especially for converting gun fired oil designed furnaces and boilers Due consideration was given to making it as simple easy to install and service as possible without weakening its d...

Страница 7: ...00 29 31 64 41290 8 203 2 X 8 203 2 plus back up of plus 1 1 2 38 1mm 120 000 35 17 72 1 4 46610 8 1 2 215 9 x 8 1 2 215 9 1 1 2 38 1mm magnesia 140 000 41 03 81 52260 9 228 6 x 9 228 6 or more loose...

Страница 8: ...ll piping must comply with local codes and ordinances or the National Fuel Gas Code ANSI Z223 1 1984 and NFPA No 54 A sediment trap or drip leg must be installed in the supply line to the burner A uni...

Страница 9: ...8 9 525 3 8 9 525 9 16 14 29 1 2 12 7 1 2 12 7 3 4 19 05 3 4 19 05 1 2 9 16 14 29 13 16 20 64 1 25 4 9 16 14 29 1 25 4 PIPE CAPACITY TABLE Nominal Diameter of Pipe in Inches mm 3 4 19 05 1 25 4 1 1 4...

Страница 10: ...it snaps Repeat this until the pilot lights Note this may take some time until all the air is bled out of the line 7 Hold the red button on the valve for 60 seconds then release 8 Observe pilot if not...

Страница 11: ...10 P265DI JUNCTION BOX ROTATED JUNCTION BOX NOT ROTATED COMBINATION GAS VALVE P265DI...

Страница 12: ...primary air both of which could be caused by over firing The only answer is to reduce the firing rate or increase the primary air Combustion efficiency is determined by the percent CO2 and the tempera...

Страница 13: ...liquids The flow of combustion and ventilating air to the burner must not be blocked or obstructed in any manner CLEANING OF BURNERS Remove the burner from the appliance and visually inspect the blas...

Страница 14: ...the flame current also holds the safety lockout timer in the reset or normal operating condition SAFETY LOCKOUT TIME S8600 only The safety lockout timer circuit starts timing the moment the trial for...

Страница 15: ...t burner lights Module senses flame current OR Pilot burner does not light Module Response S8600A F Ignition spark continues pilot valve remains S8610A F open until system is reset S8600B H After 15 o...

Страница 16: ...that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace the module NOTE If S8600B H S8610B H goes into lockout reset system For S8600M wait 6 min nom f...

Страница 17: ...On a call for heat voltage is applied to the ignitor across Terminals 1 power and 6 ground of the input connector A high voltage spark is then generated from the spark electrode to ground Simultaneous...

Страница 18: ...ILABLE AND YOU ARE A CERTIFIED INSTALLER I VOLT METER VOLTS OHMS CONTINUITY 2 AMP METER CLAMP TYPE 3 BURNER MANUAL 4 MANOMETER 5 BLADE SCREW DRIVERS 6 NUT DRIVERS 7 OPEN END WRENCHS 8 TAPE MEASURE The...

Страница 19: ...volts are present on the coil side but we do not have 115 volts on the contact side of the relay then check the voltage supply or look for a blown fuse The 115 volts are supplied from LI Hot and L2 N...

Страница 20: ...on junction box have shorted to the junction box E Bad Thermostat F Blower wheel Jammed G Excessive amount of debris stuck in blower wheel blades H 24 volt transformer is not functioning properly I T...

Страница 21: ...20 WIRING TROUBLESHOOTING DIAGRAM HONEYWELL S87KDI OPERATING SYSTEM...

Страница 22: ...or should be relocated to an area that is within this temperature range 8 Relative Humidity The S87K is coated for moisture resistance from 5 95 relative humidity at 90 F 32 C Caution should be taken...

Страница 23: ...t Spark DI 1 62898 001 Orifice Holder 5 127mm Units 1 60249 Orifice Holder 8 203 2mm Units 1 60250 Orifice Holder 11 279 4mm Units 1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 61455...

Страница 24: ...1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 60680 002 Pilot Orifice Natural gas 1 60680 Pilot Orifice LP gas 1 60987 Thermocouple 1 61818 Flamespreader 1 63213 001 Piezo Spark Gener...

Страница 25: ...his LIMITED WARRANTY by WAYNE shall be repaired or replaced at WAYNE s sole option 3 WAYNE is not responsible for any labor cost for the removal and replacement of said burner or burner components and...

Страница 26: ...25 Notes...

Отзывы: