background image

9

ADJUSTMENT OF BURNER

Starting the burner:

1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”. Figure 9.

2. Set room thermostat above room temperature and let burner run five minutes to purge the unburned gas from the unit.

3. Set thermostat below room temperature.

4. Turn gas valve control to “PILOT”.

5. Depress red button on valve to start pilot gas flow.

6. Push red button down on spark generator until it snaps.  Repeat this until the pilot lights. Note: this may take some time

until all the air is “bled” out of the line.

7. Hold the red button on the valve for 60 seconds, then release.

8. Observe pilot - if not lit, SHUT OFF BURNER COMPLETELY AND WAIT 5 MINUTES. Repeat steps 1 through 7.

9. Turn gas control valves to “ON”.

10. Set room thermostat higher than room temperature so that the burner will start.

To put burner out of operation

1. Depress the gas valve control knob on the combination gas valve and turn to “OFF”.

2. Turn off electrical supply.

STANDING PILOT

ELECTRONIC PILOT

COMBINATION GAS VALVE

COMBINATION GAS VALVE

FIGURE 9

FIGURE 11

Содержание P265DI

Страница 1: ...store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical sw...

Страница 2: ...have been heated adequately without wide variations in temperature without objectionable drafts and without excessive fuel costs in the past If the heating system is deficient with respect to any of t...

Страница 3: ...plugs or any other condition which might make the unit unsatisfactory for gas conversion is found proper arrangements should be made for replacement or repair before proceeding with the burner install...

Страница 4: ...ssure point adjuster Insert in slot cut in flue pipe When adjustment is completed scribe a line on adjuster so it can be relocated Remove adjuster trim off excess slit remainder vertically and bend se...

Страница 5: ...152 4mm 180 000 52 75 250 000 73 27 7 inch 177 8mm NOTE If the flue pipe exceeds 10 ft 3 048m in length or contains more than two elbows use next size larger pipe and draft hood NO MOVEABLE FLUE PIPE...

Страница 6: ...er was designed especially for converting gun fired oil designed furnaces and boilers Due consideration was given to making it as simple easy to install and service as possible without weakening its d...

Страница 7: ...00 29 31 64 41290 8 203 2 X 8 203 2 plus back up of plus 1 1 2 38 1mm 120 000 35 17 72 1 4 46610 8 1 2 215 9 x 8 1 2 215 9 1 1 2 38 1mm magnesia 140 000 41 03 81 52260 9 228 6 x 9 228 6 or more loose...

Страница 8: ...ll piping must comply with local codes and ordinances or the National Fuel Gas Code ANSI Z223 1 1984 and NFPA No 54 A sediment trap or drip leg must be installed in the supply line to the burner A uni...

Страница 9: ...8 9 525 3 8 9 525 9 16 14 29 1 2 12 7 1 2 12 7 3 4 19 05 3 4 19 05 1 2 9 16 14 29 13 16 20 64 1 25 4 9 16 14 29 1 25 4 PIPE CAPACITY TABLE Nominal Diameter of Pipe in Inches mm 3 4 19 05 1 25 4 1 1 4...

Страница 10: ...it snaps Repeat this until the pilot lights Note this may take some time until all the air is bled out of the line 7 Hold the red button on the valve for 60 seconds then release 8 Observe pilot if not...

Страница 11: ...10 P265DI JUNCTION BOX ROTATED JUNCTION BOX NOT ROTATED COMBINATION GAS VALVE P265DI...

Страница 12: ...primary air both of which could be caused by over firing The only answer is to reduce the firing rate or increase the primary air Combustion efficiency is determined by the percent CO2 and the tempera...

Страница 13: ...liquids The flow of combustion and ventilating air to the burner must not be blocked or obstructed in any manner CLEANING OF BURNERS Remove the burner from the appliance and visually inspect the blas...

Страница 14: ...the flame current also holds the safety lockout timer in the reset or normal operating condition SAFETY LOCKOUT TIME S8600 only The safety lockout timer circuit starts timing the moment the trial for...

Страница 15: ...t burner lights Module senses flame current OR Pilot burner does not light Module Response S8600A F Ignition spark continues pilot valve remains S8610A F open until system is reset S8600B H After 15 o...

Страница 16: ...that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace the module NOTE If S8600B H S8610B H goes into lockout reset system For S8600M wait 6 min nom f...

Страница 17: ...On a call for heat voltage is applied to the ignitor across Terminals 1 power and 6 ground of the input connector A high voltage spark is then generated from the spark electrode to ground Simultaneous...

Страница 18: ...ILABLE AND YOU ARE A CERTIFIED INSTALLER I VOLT METER VOLTS OHMS CONTINUITY 2 AMP METER CLAMP TYPE 3 BURNER MANUAL 4 MANOMETER 5 BLADE SCREW DRIVERS 6 NUT DRIVERS 7 OPEN END WRENCHS 8 TAPE MEASURE The...

Страница 19: ...volts are present on the coil side but we do not have 115 volts on the contact side of the relay then check the voltage supply or look for a blown fuse The 115 volts are supplied from LI Hot and L2 N...

Страница 20: ...on junction box have shorted to the junction box E Bad Thermostat F Blower wheel Jammed G Excessive amount of debris stuck in blower wheel blades H 24 volt transformer is not functioning properly I T...

Страница 21: ...20 WIRING TROUBLESHOOTING DIAGRAM HONEYWELL S87KDI OPERATING SYSTEM...

Страница 22: ...or should be relocated to an area that is within this temperature range 8 Relative Humidity The S87K is coated for moisture resistance from 5 95 relative humidity at 90 F 32 C Caution should be taken...

Страница 23: ...t Spark DI 1 62898 001 Orifice Holder 5 127mm Units 1 60249 Orifice Holder 8 203 2mm Units 1 60250 Orifice Holder 11 279 4mm Units 1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 61455...

Страница 24: ...1 See Chart Orifices Natural gas 1 See Chart Orifices LP gas 1 60680 002 Pilot Orifice Natural gas 1 60680 Pilot Orifice LP gas 1 60987 Thermocouple 1 61818 Flamespreader 1 63213 001 Piezo Spark Gener...

Страница 25: ...his LIMITED WARRANTY by WAYNE shall be repaired or replaced at WAYNE s sole option 3 WAYNE is not responsible for any labor cost for the removal and replacement of said burner or burner components and...

Страница 26: ...25 Notes...

Отзывы: