background image

5

 

Disconnect power and release all pressure from  

  the system before attempting to install, service, 

relocate or perform any maintenance. Lock the power disconnect in the open 

(OFF) position. Tag the power disconnect to prevent unexpected application of 

power.
 

Protect the pump from freezing during winter  

 

 conditions.

DRAINING THE PUMP

Drain openings are provided on all models.
To drain the pump:
1.   Remove drain plug and prime plug to vent the system (see 

Figure 5).

2.   Drain all piping to a point below the freeze line.

DRAINING THE TANK

Conventional tanks can be drained by opening an outlet at 

the lowest point in the system. Remove plug or the air volume 

control to vent the tank.
Precharged tanks force virtually all the water from the tank when 

system pressure is released. No draining is necessary.

RESTARTING PUMP

If the pump has been serviced, drained or has not been used for 

some time, be sure there is water in the pump housing (volute) 

and the piping to the well. There must be water in the pump 

housing (volute) at all times when the pump is running to avoid 

internal damage of seal members.

WATERLOGGED TANKS: CONVENTIONAL

When a tank system has an inadequate ratio of air and water, the 

pump will start and stop often and eradically.
1.   Disconnect the power to the pump.
2.   Open the lowest faucet in the system to release all 

pressurized water in the system.

3.   Prime the pump (Priming the Shallow Well Pump on page 4).
4.   Reconnect the power to the pump.

NOTE: 

As the pump refills the tank with water, the air volume 

control supplies the tank with the correct air to water ratio for the 

system to operate. If the air volume control is good, the pump 

will shut off at the desired cut-off and will be adjusted correctly.

WATERLOGGED TANKS: PRECHARGED

If a precharged tank becomes waterlogged, the bladder is 

normally leaking or broken.
1.   Test the tank by depressing the air valve. The air valve will 

expel water if the bladder is broken.

2.   If broken, replace the tank.

NOTE:

 Once a bladder is leaking or broken, the bladder cannot 

be repaired. The tank must be replaced.

LUBRICATION

The bearings used in the pumps are lifetime lubricated at the 

factory and require no additional lubrication.

PRECHARGED TANK

Some air is lost through the bladder in any tank. To prevent tank 

failure, check the tank precharge on a yearly basis.
1.   Disconnect power to the pump, so water does not refill the 

precharged tank.

2.   Open a faucet nearest the tank and allow all water to drain 

from the tank.

3.   Measure the tank precharge at the valve stem using a tire 

gauge.

4.   If necessary, adjust the precharge with an air pump 28 - 30 

psi on 1/2, 3/4 and 1 HP pumps.

5.   Reconnect power to the pump.

MAINTENANCE

www.waynepumps.com

SWS Systems

Operating Instructions and Parts Manual

Figure 5 - Precharged Storage Tank

DISCHARGE

NOZZLE CLEAN 

OUT

PRIME PLUG

28-30 PSI 1/2 HP, 

3/4 HP & 1 HP

DRAIN FITTING

Figure 4 - Vertical Tank

AIR VOLUME

AIR VOLUME CONTROL

HOSE COUPLING

OUTLET

Figure 6 - Voltage Selector

Содержание 64043-WYN1

Страница 1: ...d protect from sharp objects hot surfaces oil and chemicals Replace damaged or worn cords immediately 15 Keep fingers and foreign objects away from ventilation and other openings Do NOT insert any obj...

Страница 2: ...llon precharged tank will have the same usable water or drawdown capacity as a 40 gallon conventional tank but the tank is smaller in size Figure 1 PRESSURE SWITCH The pressure switch provides for aut...

Страница 3: ...the pipe and cause abnormal pump operation Make sure to use pipe joint compound on all male pipe threads DUG WELL CISTERN LAKE AND SPRING INSTALLATION FIGURE 12 ON PAGE 9 1 Install a foot valve on in...

Страница 4: ...o the metal well casing or use a ground electrode furnished by the power company There is only one proper ground terminal on the unit The terminal s is located under the pressure switch cover is paint...

Страница 5: ...Priming the Shallow Well Pump on page 4 4 Reconnect the power to the pump NOTE As the pump refills the tank with water the air volume control supplies the tank with the correct air to water ratio for...

Страница 6: ...so the two screw holes are on a horizontal line across the motor shaft Figure 10 This placement should be done to ensure proper draining and priming 3 Place rotating shaft seal member in position on i...

Страница 7: ...ed to keep the ceramic face clean You can use a little water or dish soap to lubricate the seal pocket to make assembly easier 16 Slide the square cut gasket over the flange on the seal plate make sur...

Страница 8: ...ed 6 Replace air volume control 7 Foot valve may be clogged or stuck closed 7 Clean or replace as needed 8 Pump not fully primed 8 Continue priming paus ing ev ery 5 minutes to cool pump body Refill p...

Страница 9: ...rick stone or concrete to prevent cave in D DRIVEN WELL Pipe with a pointed screen is driven into the ground below the water table The depth is usually less than 50 feet Available diameters are 1 thro...

Страница 10: ...e been damaged as a result of accident abuse misuse neglect improper installation improper maintenance or failure to operate in accordance with Wayne Water Systems written instructions THERE IS NO OTH...

Страница 11: ...es aceite y qu micos Reemplace los cables da ados o desgastados de inmediato 15 Mantenga los dedos y objetos extra os lejos de la ventilaci n y otras aberturas NO inserte ning n objeto en el motor Rie...

Страница 12: ...n tanque precargado de 20 galones rendir la misma cantidad de agua utilizable o capacidad de vaciado que un tanque convencional de 40 galones con la ventaja de que el tanque es m s peque o Figura 1 PR...

Страница 13: ...de pedestal tipo tap n siga las instrucciones del fabricante Como alternativa se puede usar una v lvula de retenci n en l nea con un pozo accionado Figura 2 Ilustraci n C La tuber a entre la v lvula d...

Страница 14: ...r nea met lica o una cubierta de pozo de al menos 10 pies largo son los mejores electrodos de tierra Si se usa tuber a de pl stico o adaptadores con aislamiento pase un cable directamente a la armaz n...

Страница 15: ...agua el control de volumen de aire suministra al tanque la relaci n adecuada de aire y agua para que el sistema funcione Si el control de volumen de aire est bien la bomba se apagar en el nivel l mite...

Страница 16: ...rizontal a trav s del eje del motor Figura 10 Esta ubicaci n se debe hacer para asegurar un drenaje y cebado adecuados 3 Sit e la pieza giratoria del sello del eje en el impulsor y presi nela para que...

Страница 17: ...Se puede utilizar un poco de jab n y agua o un plato para lubricar el sello de bolsillo para facilitar el montaje 16 Deslice la junta de corte cuadrado sobre la brida en la placa de sellado aseg rese...

Страница 18: ...de aire 7 La v lvula de pedestal puede estar obstruida o atascada 7 Limpie o reemplace de ser necesario 8 La bomba no est totalmente cebada 8 Contin e cebando pausando 5 minutos para enfriar el cuerp...

Страница 19: ...D O Se acci ona una t uber a con una pant al l a con punt a en l a t i er r a por debaj o de l a capa f r e t i ca La pr of undi dad por l o gener al es m enor a 15 25 m 50 pi es Los di m et r os com...

Страница 20: ...idente abuso mal uso negligencia instalaci n incorrecta mantenimiento inadecuado o falla en operar de acuerdo con las instrucciones escritas de Wayne Water Systems NO EXISTE NINGUNA OTRA GARANT A EXPR...

Отзывы: