Wavin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
Wavin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
41
Design Manual
TELEPHONE
+31 (38) 4294911
4
www.wavin.com
P
Prro
ob
blle
em
m
WTC3 is not working
(Power LED is not lighting)
DRT200 are not respond
(neither of LED has activity)
DRT200 is not respond for any
touch but the LED s are lighting
Can not change the
heating/cooling mode at the
master DRT-200
Can not change the economy
mode to comfort mode at the
DRT-200
Can not turn ON the DRT-200
In case of H/C change over the
valves are not react immediatelly.
The control LED is fleshing on
WTC-3
A WTC3 detecting condensation,
while the surface of dew point
sensor is dry . (Yellow LED is
lighting on WTC-3)
The sign of dew point sensor not
the right actuator is close the
circuit
C
Ca
au
us
se
e
The unit is no get any
voltage
No connection between
WTC-3 and DRT-200
Not the right program
has been selected
The addressing of
DRT-200 is not
correct
Input for change over is not
selected properly
Needs to be configure
Needs to be configure
Change over is in
progress
Shortcut in the wire of
dew point sensor
The dew point sensor is not
connected to the right input
R
Re
em
me
ed
dy
y
Check connection of electric
power at plug 1 and 2 with
measurement unit
Check the connection between
the 46-47 plug of WTC-3 and
3-4plug of DRT-200 (polarity,
demage, shortcut).
Reversed polarity NOT allowed!
Check the program setting on
program selector at back side of
WTC-3
Set the proper address for every
DRT-200 (1..7). check the status of
every connected DRT-200 via
configuration program
According to the factory default the
master DRT-200 can change only
the H/C mode.
Check the settings of H/C change
over with configuration program
Check the settings of C/E change
over with configuration program
Check the settings of ON/OFF
change over with configuration
program
This is not a fault. WTC-3 is in
change over mode. Wait until the
delay is in progress (default: 10
minutes
Disconnect the dew point sensor.
The condensation sign must to
finish at WTC-3. Check the wire
for demage, brake or shortcut.
Check the connection. This could
happen only in case if the dew
point sensor are connected directly
to the WTC-3
1
10
0.. T
Tr
ro
ou
ub
blle
es
sh
ho
oo
ottiin
ng
g