EuroPEK Filter -
Oil Separator
24BI01ae
WAVIN-LABKO LTD
8
5.
If the system is to be equipped with a EuroNOK sampling shaft including a shut-off
valve, see separate installation instructions for the sampling and shut-off valve shaft
EuroNOK as well as the instructions laminated onto the side of the shaft.
6.
Install the inlets and outlets of the separator.
7.
Install rubber gaskets onto the bottom edge of the EuroHUK maintenance shaft(s).
Install the EuroHUK maintenance shafts in a vertical position into the installation
frame of the separator. Lock the retaining latches. See figure 3.
Attach the GRP- maintenance shafts (GRP HUK 600) into the installation frame. Do
not let the gasket slip off its groove. Certain lubricants contribute to an easier
installation of the GRP- maintenance shafts.
8.
Install the ventilation pipes onto the ventilation outlets on the maintenance shafts.
9.
Install the cable protection tube into the cable penetration at the top of the
maintenance shaft. The probe cable should be pulled into the building through the
cable protection tube. Leave enough cable inside the maintenance shaft to lift the
probe on the ground surface for maintenance operations.
10.
Continue compacting the sand in 40 cm layers until the ground level is reached.
Avoid the use of heavy vibration when compacting sand layers on top of the tank or
its inlets and outlets.
11.
After filling the pit, cut the maintenance shaft in a proper height. Note that the cover
and frame will give about 100 mm extra height for the maintenance shaft.
12.
Attach the metal hook for the connection box at the upper edge of the maintenance
shaft. The hook will be positioned between the maintenance shaft and the frame of
the cast iron cover.
13.
Set the flange for hanging the alarm probe at edge of the maintenance shaft (See
figure 2). The flange is set at the level next to the oil skimming pipe, in the frame of
the EuroHUK.
Figure 2. The position of the flange for hanging the alarm probe
14.
The metallic filter frames are connected to each other by a grounding wire. The
grounding wire runs on the inner surface of the tank leading to the metal bolt on the