Heating/Cooling control unit FBC-HC 

 

 IMPORTANT! 

It is strongly recommended that both the installer and end user should care-

fully read and understand the installation and operation manual, prior to 

commencing installation. 

 

The control units FBC-HC must only be mounted operated and maintained 

by a qualified fitter; failure to comply with this condition could render the 

manufacturers warranty obsolete. 

 

The manufacturer shall not be responsible for any incompetent use of the 

FBC-HC and appropriate observance of all instructions in the above manual 

is considered mandatory. “For reasons of safety” modifications to the unit 

are not permitted and repairs if necessary must only be carried out with approval by the manufacturer.  

 

The temperature range and the contents of the set depend on the model and equipment. 

  

Subject to technical modification. 

1.

 

INTENDED USE 

1

 

2.

 

REFERENCES, SYMBOLS AND ABBREVIATIONS 

2

 

3.

 

SAFETY INSTRUCTIONS 

2

 

4.

 

DESIGN 

2

 

5.

 

INSTALLATION AND ELECTRICAL CONNECTION 

2

 

5.1.

 

M

OUNTING AND 

H

YDRAULIC CONNECTIONS

 

2

 

5.2.

 

E

LECTRICAL CONNECTION

 

3

 

6.

 

TECHNICAL DATA 

3

 

7.

 

MATERIALS 

4

 

8.

 

TROUBLE SHOOTING 

4

 

 
 

1.  INTENDED USE 

  The hydraulic control unit FBC-HC is used for variable flow temperature control of the supply temperature in floor 

and panel heating/cooling systems. The required flow temperature is controlled in conjunction with the outside 

temperature according to a selectable curve. The inclination of this heating/cooling curve can be selected due to 

the local climatic conditions. 

  With the heating-cooling controller CC-HC the system can either be operated solely in  heating mode, cooling 

mode or in combined mode of heating and cooling. The heating / cooling commutation can be done manually or 

via an external switching signal (e.g. from a reversible heat pump, etc.). 

  With the controller CC-HC the operation of water surface heating / cooling system can be adjusted to the individ-

ual needs of the installation. Particularly suitable for the regulation of single-family homes or different units in 

apartment buildings with individual user behaviour. The controller has a 7-day programming with 9 factory-set in-

tegrated standard programs as well as 4 programs which can be set as required by the user.  

  A room temperature controller can optionally be connected to the CC-HC climate controller. Suitable cable based 

or radio-controlled programmable room thermostats are available as accessories. These enable heating/cooling 

system operation to be optimised based on the usage pattern of a reference room. 

  The FBC-HC have been designed for use in dry environments, e.g. in residential rooms, office spaces and indus-

trial facilities. Usually it is installed in the central heating room. 

  Verify that the installation complies with existing regulations before operation to ensure proper use of the installa-

tion.  

  If the control unit FBC-HC is used in systems with cooling function, then it might be associated with a suitable 

and properly affixed insulation to prevent condensation on the control unit or pipes. 

 

The included heat insulation box may be used only for heating purposes. Local regulations regarding heat / cold 

insulation must be considered and also to be observed.

 

 

Fig.1 

Содержание FBC-HC

Страница 1: ...g curve can be selected due to the local climatic conditions With the heating cooling controller CC HC the system can either be operated solely in heating mode cooling mode or in combined mode of heating and cooling The heating cooling commutation can be done manually or via an external switching signal e g from a reversible heat pump etc With the controller CC HC the operation of water surface he...

Страница 2: ...the sensors and the 230V connections under any circumstances Inter changing these connections may result in life endangering electrical hazards or the destruction of the appliance and the connected sensors and other appliances 4 DESIGN 1 Ball valve supply with gravity flow stop supply sensor connection red ball valve handle L 92 thermometer 0 120 C 2 circulation pump 3 valve drive 4 3 way mixing v...

Страница 3: ...ating temperature 0 90 C 1 Max operating pressure 6 bar Power supply 230 VAC Power consumption pump 1 1 Please refer also to technical leaflets of the pump Control CC HC Power supply 230 VAC 10 50 Hz Max operating temperature 0 50 C Temperature precision 0 1 C Regulation characteristics Non linear PID Intelligent 3 point valve drive finds the operating point Degree of protection IP 30 Protection c...

Страница 4: ...x 5 10 K The control unit may be ready for operation sooner if the TB is removed for a short time to allow it to cool down more quickly to reach the switching temperature 1 2 The temperature of the boiler s supply water is lower than the required flow temperature of the UFH Set the boiler s supply water temperature to a higher value 2 THE SUPPLY WATER TEMPERATURE CANNOT BE SET TO THE REQUIRED VALU...

Отзывы: