background image

 

MuB_xx_FBC-HC_EN_2011-08-16 

Subject to technical modifications! 

page 4 

EN 

Valve drive  

NR230-00 

 

ARA 661 

Power supply: 

230 VAC ±15 %, 50/60 Hz   

230 VAC, 50 Hz 

Power consumption: 

2,5 VA 

 

5 VA 

Degree of protection: 

n/a 

 

IP 41 

Protection class: 

II 

 

II 

Connection: 

Wires, 3 × 0,75 mm² 

 

Wires, 3 × 0,75 mm² 

Angle of rotation: 

90° electrically limited 

 

90° 

Torque: 

5 Nm  

 

6 Nm 

Running time: 

140 s (50 Hz) 

 

120 s / 90° 

Direction of rotation: 

selectable on terminals 

Manual operation: 

mechanical disengagement 

Indication of position: 

yes, reversible scale 

Ambient temperature: 

0…+50 °C 

 

-5…+55 °C 

EMC: 

CE accord. 89/336/EWG 

 

EMC 86/336/EEC 

Low voltage directive: 

CE accord. 73/23/EWG 

 

LVD 2006/95/EC 

Maintenance: 

maintenance free 

 

n/a 

 

7.  MATERIALS 

Valves / fittings: 

Brass Ms 58 

Pipes: 

Precision steel pipe, coated 

Plastic: 

Impact- and temperature resistant  

Gaskets: 

EPDM-Elastomers or AFM 34 

O-Rings: 

EPDM 

 

8.  TROUBLE SHOOTING 

X.  PROBLEM 
X.X 

Possible cause 

Solution 

1.  HEATING CIRCUIT IS NOT GETTING WARM 
1.1  

The optional temperature limiter (TB) has switched off 

the pump (UWP). 

Cause: TB is set to a very low value. 

Set the TB by approximately 10 K higher than the re-

quired flow temperature. 

 Take into consideration the max. admissible flow 

temperature! 

 Differential gap of the TB: approx. 5 - 10 K. 

 The control unit may be ready for operation sooner 

if the TB is removed for a short time to allow it to cool 

down more quickly to reach the switching temperature. 

1.2 

 

The temperature of the boiler’s supply water is lower 

than the required flow temperature of the UFH. 

Set the boiler's supply water temperature to a higher 

value.  

2.  THE SUPPLY WATER TEMPERATURE CANNOT BE SET TO THE REQUIRED VALUE OR IT FLUCTU-

ATES WITHIN A VERY WIDE RANGE 

2.1 

The control unit’s SUPPLY and RETURN are not cor-

rectly connected. 

Check all inlets and outlets of the control unit for cor-

rect connection. Please take into account Fig. 3.  

2.2 

The circulating pump’s pressure head/pump stage is 

set at a very low value. 

Increase the rotation frequency, the pump’s pressure 

head/pump stage, respectively. 

2.3 

The heating load is too big for the control unit used, 

i.e., the heat consumption exceeds the rated power of 

the control unit. This state may set in temporarily, e.g., 

in case of heating a “cold” floor for the first time. 

Check the maximum heat consumption and compare it 

with the rated power. If necessary, distribute the heat-

ing circuits to a second control unit / heating circuit. 

If the cause is in the initial heating up of a given floor 

heating system, the function may be normalized after 

the heating up phase. This is possible when the heat-

ing load is at maximum and will then take longer to 

achieve the required temperature. 

 

Содержание FBC-HC

Страница 1: ...g curve can be selected due to the local climatic conditions With the heating cooling controller CC HC the system can either be operated solely in heating mode cooling mode or in combined mode of heating and cooling The heating cooling commutation can be done manually or via an external switching signal e g from a reversible heat pump etc With the controller CC HC the operation of water surface he...

Страница 2: ...the sensors and the 230V connections under any circumstances Inter changing these connections may result in life endangering electrical hazards or the destruction of the appliance and the connected sensors and other appliances 4 DESIGN 1 Ball valve supply with gravity flow stop supply sensor connection red ball valve handle L 92 thermometer 0 120 C 2 circulation pump 3 valve drive 4 3 way mixing v...

Страница 3: ...ating temperature 0 90 C 1 Max operating pressure 6 bar Power supply 230 VAC Power consumption pump 1 1 Please refer also to technical leaflets of the pump Control CC HC Power supply 230 VAC 10 50 Hz Max operating temperature 0 50 C Temperature precision 0 1 C Regulation characteristics Non linear PID Intelligent 3 point valve drive finds the operating point Degree of protection IP 30 Protection c...

Страница 4: ...x 5 10 K The control unit may be ready for operation sooner if the TB is removed for a short time to allow it to cool down more quickly to reach the switching temperature 1 2 The temperature of the boiler s supply water is lower than the required flow temperature of the UFH Set the boiler s supply water temperature to a higher value 2 THE SUPPLY WATER TEMPERATURE CANNOT BE SET TO THE REQUIRED VALU...

Отзывы: