background image

Each WattStopper BZ series power 
pack can supply power for 4 UT-305 
sensors. When using more sensors 
than this, multiple power packs are 
required.
Refer to the wiring diagram on the next 
page for the following procedures:

Connect the 

low voltage

•  RED wire (+24VDC) from power pack  
  to the +

24V

 terminal on the sensor.

•  BLACK wire (Return) from power  

  pack to 

Common

 terminal on the  

 sensor.

Wiring a 

SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY

–connect:

•   BLUE wire from power pack to Control Out terminal on sensor.

To add a 

MANUAL SWITCH such as the LVS-1 Momentary Toggle Switch, or RS2-3 

Low Voltage Momentary Switch to the above applications–connect:
•  Wire from one side of switch to Common terminal on sensor.
•  Wire from other side of switch to Man Switch terminal on sensor.

WIRING DIRECTIONS

  

CAUTION

  

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE 

INSTALLING POWER PACKS OR SENSORS.

Call 800.879.8585 for Technical Support

UT-305

Ultrasonic

Occupancy Sensor

U.S.Patents:

5,640,113

Patent Pending

40kHz Ultrasonic

+24VDC/VAC

Connect to Watt Stopper 

Class 2 Power Packs

For Indoor Use Only

03624r2

Control Out.

Man. Switch

+24V

Common

LISTED

88T9

Appliance

Control

www.wattstopper.com

800.879.8585

Содержание UT-305

Страница 1: ...to 55 C Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec upon intial power up or DIP switch reset Ultrasonic Coverage Model UT 305 1 up to 500 ft 2 Model UT 305 2 up to 1000 ft 2 Model UT 305 3 up to 2000 ft 2 Sensitivity Adjustment Minimum to Maximum trimpot Frequency 40kHz Installation Instructions UT 305 Ultrasonic Low Voltage Occupan...

Страница 2: ...lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The UT 305 operates on 24V supplied by Watt Stopper Power Packs The sensors can operate on 24VDC 24VAC or half wave rectified AC COVERAGE PATTERN The UT 305 is available in 3 models Each model has a different size coverage pattern The coverage shown represents walking motion at a mounting height o...

Страница 3: ...nsor to the ceiling The UT 305 is designed for a ceiling height of about 8 10 feet Mounting above or below this range will significantly affect the coverage patterns As a general rule each occupant should be able to clearly view the sensor Open Office Area Coverage To get complete coverage in an open office area install multiple sensors so that there is approximately 20 overlap with each adjacent ...

Страница 4: ...al on sensor To add a MANUAL SWITCH such as the LVS 1 Momentary Toggle Switch or RS2 3 Low Voltage Momentary Switch to the above applications connect Wire from one side of switch to Common terminal on sensor Wire from other side of switch to Man Switch terminal on sensor WIRING DIRECTIONS CAUTION TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS Call 800 879 8585 for T...

Страница 5: ...Color Legend Load 1 Load 2 Optional UT 305 Rear Housing Depluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out 24V Common Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Black Red 1 2 Line Voltage Switches Standard wiring with local off switch ...

Страница 6: ...pluggable Terminal Front Cover Ceiling Spring Clips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red UT 305 Common For low voltage momentary switch set DIP switch 1 ON Man Switch Jumper Back of LVS 1 Common White Black Red Line Voltage Wire Color Legend ...

Страница 7: ...front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low voltage wires to the appropriate terminals on the sensor 3 Loosen the appliance mounting screws attached to the J Box 4 Align the sensor in the J Box so that the mounting screws on the box match the key holes on the sensor s rear housin...

Страница 8: ...wise 4 Remain still The LED should not flash The lights should turn off after 5 seconds If not see Troubleshooting 5 Move about the coverage area The lights should come on Adjust the Ultrasonic Sensitivity as necessary to provide the desired coverage Green LED indicates activation from the ultrasonic sensor When testing and adjustment is complete reset DIP Switches to the desired settings and repl...

Страница 9: ...ic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load can be turned ON by manual switch activation and it stays on as long as occupancy is detected The sensor time delay operates as programmed When the load turns OFF due to lack of occupancy detection the load can be turned ON again by occupancy de...

Страница 10: ... starts when no motion is detected After no motion is detected for the length of the time delay the sensor will turn the lights off The sensor can select the time delay using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately and is refined continually as h...

Страница 11: ... may be experiencing activations from outside the controlled area or from some type of interference see Unwanted Sensor Activations below 2 Check all sensor wire connections 3 Disconnect power pack s blue wire If the lights do not turn off replace power pack Reconnect blue wire If the lights turn off the problem may be in the sensor to check Reconnect the blue wire Turn sensitivity and time delay ...

Страница 12: ... 305 2 Ultrasonic Occupancy Sensor up to 1000 sq ft coverage Low Voltage UT 305 3 Ultrasonic Occupancy Sensor up to 2000 sq ft coverage Low Voltage UT 300 1 2 3 Ultrasonic Occupancy Sensor Low Voltage w Isolated Relay and Manual On feature BZ 50 Power Pack 120 277VAC 50 60Hz 225mA 20A ballast or incandescent 1HP 120 250VAC BZ 150 Power Pack 120 277VAC 50 60Hz 225mA 20A ballast or incandescent 1HP ...

Страница 13: ...ities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 2800 De La Cruz Boulevard Santa Clara CA 95050 800 879 8585 www wattstopper com 03631r4 9 2013 Please Recycle ...

Отзывы: