TROUBLESHOOTING

Lights do not turn ON with motion (LED does flash)

1.  Press and release each button to make sure that the correct lights come 

ON

 for each relay. 

If the lights do NOT turn ON

, check wire connections, 

especially the Load connection. 

If the lights turn ON

, verify that the 

correct On Mode is selected in DIP switches 8 and 9.

2.  Check to see if light level control is enabled: cover the sensor lens with 

your hand. If the lights come 

ON

, adjust the light level setting. 

3.  If lights still do not turn 

ON

, call 800.879.8585 for technical support.

Lights do not turn ON with motion (LED does not flash)

1.  Press and release each button to make sure that the correct lights come 

ON

 for each relay. If the lights turn 

ON

, verify that Sensitivity is on High.

2.  Check the wire connections, in particular, the Line connection. Verify that 

connections are tightly secured. 

3.  If lights still do not turn 

ON

, call 800.879.8585 for technical support.

ADJUSTMENTS

Sensor Adjustment

Remove the wall plate. Remove the button cap by firmly squeezing together the 

top sides of the button assembly. Gently pull it away from the unit. 
When the adjustments are completed, replace the button cap by inserting its 

hinges into the tabs on the main unit and then squeeze the top of the button while 

pressing it into the unit. Reinstall the cover plate.

Light Level Adjustment

The light level can be set with loads 

ON 

or 

OFF

. To enable light level control and 

set the threshold: 1) Make sure the room is lit appropriately. 2) Put the sensor 

into TEST mode (see Time Delay switches). You have 10 minutes to complete the 

procedure. 3) Press and hold the ON/OFF button (Relay 

1

 button on the PW-302) 

for 3 seconds, until you hear a beep. 4) Step away from the sensor. After 10 

seconds a beep sounds, indicating that the threshold level is set. This threshold 

is retained, even if power is lost, until it is re-set or disabled. In the PW-302, light 

level control only affects Relay 

2

To disable light level control, press and hold the Relay 

1

 button for 

7 seconds

until a double beep tone sounds.

Reset to Default

Use the DIP Switch Settings tables on the previous page to return features 

to factory settings. To reset the PW press and hold the Relay 

1

 button

 

for 

10 

seconds

, until a triple beep sounds. This resets the sensor and disables light 

level control (the brightest ambient light will not hold the light 

OFF

).

Содержание PW-301

Страница 1: ...t E ballast LED 1 6 HP 277VAC 1200W ballast E ballast LED 1 6 HP 347VAC 1500W ballast LED 1 6 HP Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 10 min with 5 sec time delay PIR Adjustment High or Low Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual Optional Neutral All models Multi Way Capability All models Terminal scre...

Страница 2: ...and then return it to the Test setting Walk Through Mode DIP 4 ON The PW sensor turns the load OFF three minutes after the area is initially occupied if no motion is detected after the first 30 seconds If motion continues beyond the first 30 seconds the set time delay applies High DIP 5 OFF Default setting Suitable for most applications PIR Sensitivity Adjustment The PW sensor constantly monitors ...

Страница 3: ... Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW can provide audible and or visible alerts as a warning before the load turns OFF Unit will beep at one minute at 30 seconds and at 10 seconds before turning OFF load When Walk Through is active the unit beeps three times at 10 seconds before the load goes OFF If Visible Alert is also ON the one minute time out warn...

Страница 4: ...elay due to initial power up of the sensor that only occurs during installation 5 Test and adjust the sensor if necessary 6 Install industry standard decorator wall switch cover plate not included INSTALLATION Red Black Neutral Line Green Green Ground Blue Primary Load Secondary Load Neutral optional Brown Yellow Red Black Neutral Line 1 Green Green Ground Blue Primary Load Brown Secondary Load Li...

Страница 5: ...n wiring this way only use 300 series sensors Multi Way in 300 series is not compatible with prior sensor models The following princlples apply for Multi Way All units can see each other s push button events and respond accord ingly All units can see each other s PIR trigger event The response will be determined by the Light Level setting and or conditions of the space of the detecting sensor The ...

Страница 6: ...er a 30 second re trigger delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Manual ON mode must be pressed to turn the load back on un less the sensor set in Auto ON mode detects motion If the light is turned OFF manualy by pressing the ON OFF button set in Auto ON it will en...

Страница 7: ...rols load 2 Two phase wiring Black Black Neutral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Green Ground Green Green Red Brown Blue Blue Black Black Neutral Ground Green Neutral optional Line 1 Yellow Red Primary Load Brown Secondary Load Neutral optional Blue Blue Green Ground Green Green Red Brown Line 2 Neutral ...

Страница 8: ...ned ON or OFF using the ON OFF button Manual ON DIP 8 ON for Relay 1 DIP 9 ON for Relay 2 With an ON Mode DIP switch in the ON position the occupant must press the ON OFF button to turn ON the load The sensor keeps the load ON until no motion is detected for the selected time delay There is a 30 second re retrigger delay If occupancy is detected during the delay the sensor turns the load back ON A...

Страница 9: ...rough ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Test 20 min 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 1 2 3 Time Delay Service bypasses occupancy light level functions Control the load manually using ON OFF button 6 Disabled Enabled Visible Alert PW 302 ONLY 9 Auto On Manual On Relay 2 Mode 1 2 Factory Settings All models PW 301 serie...

Страница 10: ...ly pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the threshold 1 Make sure the room is lit appropria...

Страница 11: ...0 879 8585 for technical support Sensing motion outside desired areas 1 Select PIR Sensitivity Low DIP switch 5 ON if necessary 2 Mask the PIR sensor s lens to eliminate unwanted coverage area Red LED is OFF all the time and the sensor features don t work 1 Check DIP switches 1 2 3 If they are all ON the unit is in Service Mode Set the DIP switches to a valid Time Delay setting 2 If re setting the...

Страница 12: ...ities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or reinstallation 17804r3 02 2014 Please Recycle 2800 De La Cruz Boulevard Santa Clara CA 95050 800 879 8585 www wattstopper com ...

Отзывы: