background image

LMRC-102

Digital Lighting Management (DLM)

Dual Relay Room Controller

Quick St

art Guide

Corner Mount

Occupancy

Sensor

Switch

Daylighting

Sensor

Ceiling Mount

Occupancy

Sensor

Room

Controller

J Box

To

Load

DLM Local Network

(low voltage, Class 2)

LMRJ cables

PLACEMENT EXAMPLE

Input Voltage   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .120/230/277VAC, 50/60Hz
Load Requirements .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .Not to exceed 20A total
  Each relay rated for up to: 

   Incandescent .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 20A @ 120VAC 

   Ballast  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .20A @ 120/277VAC 

   Motor  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 1Hp @ 120/240VAC
Output     .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .150mA @ 24VDC
DLM Local Network Characteristics: 

  Provides low voltage power over Cat 5e cable (LMRJ) . 

  Supports up to 24 communicating devices, including 4  

  LMRC‑10x or LMPL‑101 max per each DLM Local Network . 

  Free topology up to 1,000ft of low voltage cable .
Environment: 

  Operating Temperature .  .  .  .  .  .  .  .  .  .  .  .  .  .32° to 104°F (0° to 40°C) 

  Storage Temperature   .  .  .  .  .  .  .  .  .  .  .  .  .  .23° to 176°F (‑5° to 80°C) 

  Relative Humidity .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5 to 95% (non condensing)
Patent Pending

THIS UNIT IS PRE-SET FOR PLUG n’ GO™ 

OPERATION, ADJUSTMENT IS OPTIONAL.

For full operational details, adjustment and more 

features of the product, see the DLM System Installation 

Guide provided with the LMRC-102 room controller, 

and also available at 

www.wattstopper.com 

INSTALLATION SHALL BE IN ACCORDANCE WITH ALL 

APPLICABLE REGULATIONS, LOCAL AND NEC CODES.

Wire connections shall be rated suitable for the wire 

size (lead and building wiring) employed .

CONNECTIVITY

The LMRC‑102 communicates to all other DLM 

devices connected to the DLM Local Network . 

Connection drawings are for example only . The 

low voltage LMRJ cables can connect to any DLM 

device with an open RJ45 receptacle .
All line voltage wiring is #12 AWG . Each relay is 

rated for up to 20A, total load for LMRC‑102 not 

to exceed 20A .

Line

Voltage

Room

Controller

J-Box

Daylight Sensor

Switch

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Loads

2

1

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load 1

Yellow wire

to Load 2

LMRC

102

ATTACHING CABLES

MOUNTING THE CONTROLLER

The LMRC‑102 room controller can either be mounted 

external to a junction box, placing it in the plenum space or 

mounted directly inside a 4” x 4” junction box . 

Line

J-Box

Load

    Outside  a  4”  x  4”  box                                                  Inside  a  4”  x  4”  box                                            

Loads

1

2

Line Voltage

J-Box

LMRC-102

Room

Controller

Line/Hot

Black wire

Neutral

White Wire

Red wire

to Load 1

Yellow wire

to Load 2

Remove rubber jack covers if using all 3 RJ45 receptacles . 

Leave covers in place for all unused receptacles .

J-Box

Load

Line

WARNING:

 TO CONNECT A COMPUTER TO THE 

DLM LOCAL NETWORK USE THE 

LMCI-100.  

NEVER CONNECT THE DLM 

LOCAL NETWORK TO AN ETHERNET 

PORT

 – IT MAY DAMAGE COMPUTERS 

AND OTHER CONNECTED EQUIPMENT.

For Class 2 DLM devices and device wiring:

 

To be connected to a Class 2 power source only . 

 

Do not reclassify and install as Class 1, or Power and Lighting Wiring .

 WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits .

CAUTION:

 TURN THE 

POWER OFF AT THE CIRCUIT 

BREAKER BEFORE WIRING.