TESTING AFTER INSTALLATION

To facilitate coverage testing, the factory setting for Time Delay is 12 seconds, and the Light 

Level is at Maximum.
If you want to test a sensor for intended detection or operation:

1. Make sure that the time delay is set to 12 seconds and the light level is set to maximum 

(clockwise to the sun

icon). (The dials are located on the bottom of the sensor.)

2. Adjust sensor and lamp holders to the desired position. 
3. Ensure that power has been restored to the sensor.
4. Move into the location to be tested; lights should turn on. Stand still. In about 12 seconds 

the lights should turn off. Move or walk and the lights should turn on. Repeat this process 

to test other locations. Make sensor coverage adjustments as needed (see Coverage 

adjustment and Masking, page 2).

Note: 

When power is restored to the sensor, the lights will turn on for approximately one 

minute. (See Security Override, page 9.)

Note: 

If the lights do not turn on with movement in the area after they have turned off 

in step 4, the level of daylight may be too high and the sensor’s light level adjustment is 

keeping the sensor inactive. Wait until daylight levels have reduced before testing again.

5. See Dial Adjustments, below, for guidelines to adjust the time delay and light level to the 

desired settings for operation.

DIAL ADJUSTMENTS

Time Delay

 and 

Light Level

 control dials are located on the bottom of the sensor. 

1 . Adjust Time Delay:

The time delay is the amount of time that elapses before lights turn 

off since the sensor last detected motion. This can be set from  

12 seconds to 16 minutes. For normal operation, the time delay 

should be set to 1 minute or more. 

• 

In areas where there is mostly walk through movement, the time 

delay amount can be low.

• 

In areas where people may stop and remain for periods of time,  

the time delay should be set to a higher amount, preferably 

16 minutes.

2 . Adjust Light Level:

Turning the light level adjustment dial raises or lowers a 

daylight  

level

 in the sensor. When the light of the day rises above this set level, 

the sensor becomes inactive; this keeps the lights off when there is 

enough daylight present. 

We suggest initially setting the light level adjustment to 

half way

 between 

minimum and maximum. If a different setting is desired after installation, 

then follow the Making Changes procedures, next page.

SEC.

MIN.

16

1

12

Minimum =
Maximum =

LIGHT LEVEL DIAL

SEC.

MIN.

16

1

12

TIME DELAY DIAL

Minimum: 12 seconds 

Maximum: 16 minutes

Содержание EW-200-120

Страница 1: ...P 277VAC Current Consumption Without Isolated Relay 22 mA max With Isolated Relay 34 mA max Time Delay Adjustment 12sec 16min Light Level Adjustment 0 5FC 200FC Isolated Relay on EW 200 both 120 277 models Normally Open Normally Closed contacts Isolated Relay Rating 1A 30VAC DC UL 773A Raintight Rated IEC IP 55 Rated Installation Instructions U S Patents 4 787 722 5 640 113 EW 200 EW 205 Outdoor P...

Страница 2: ...D INSTALLATION 5 DIAL ADJUSTMENTS 7 Adjust Time Delay 7 Adjust Light Level 7 Making Changes 8 SECURITY OVERRIDE 9 TROUBLESHOOTING 9 ORDERING INFORMATION 10 WARRANTY INFORMATION 10 CAUTION READ ALL OF THE INSTALLATION INSTRUCTIONS BEFORE INSTALLING THIS PRODUCT THIS UNIT USES HIGH VOLTAGE IT SHOULD ONLY BE INSTALLED BY QUALIFIED PERSONS THAT ARE THOROUGHLY FAMILIAR WITH PROPER SAFETY PROCEDURES AND...

Страница 3: ...5 270 coverage Coverage adjustment The front of the sensor housing can be moved up and down for easy coverage adjustment Call 1 800 879 8585 or 1 972 578 1699 For Technical Support 2 COVERAGE PATTERN Coverage is shown as tested in a controlled setting with the unit mounted at 8ft at a 10 tilt from the horizontal surface The actual outside coverage pattern may vary substantially at the specific ins...

Страница 4: ...er plate mounting as shown in the illustration on the right Horizontally mounted For horizontal mounting such as under eaves rotate the sensor housing as shown in the diagrams below Make sure that the gasket is seated properly Loosen the two screws at the back of the sensor Rotate the sensor housing 180 Replace and tighten the screws Check Our Web Site For FAQs www wattstopper com 3 1 2 3 Attach m...

Страница 5: ...able vibration free surface Avoid runoff sheltered locations preferred Aim motion sensor downward to limit sensing Mount motion sensor level Do not mount by vents or above lamps Mount sensor below lamps to avoid heat effects YES YES YES YES NO NO NO NO NO NO NO Call 1 800 879 8585 or 1 972 578 1699 For Technical Support YES ...

Страница 6: ...r sensor also see instructions page 6 Attach cover plate assembly and gasket to the junction box with 4 screws and screw covers supplied IMPORTANT Make sure that the gasket seats properly when attaching the cover plate Attach cover plate assembly and gasket to the junction box with 4 screws and screw covers supplied IMPORTANT Make sure that the gasket seats properly when attaching the cover plate ...

Страница 7: ...ications front cover Isolated Relay EW 200 models only See Specifications front cover for rating Connect the wires necessary to the application that requires this output ORANGE Common must be used for proper operation GREEN Normally Closed Open when occupancy is detected YELLOW Normally Open Closed when occupancy is detected Call 1 800 879 8585 or 1 972 578 1699 For Technical Support 6 Note Note W...

Страница 8: ...or inactive Wait until daylight levels have reduced before testing again 5 See Dial Adjustments below for guidelines to adjust the time delay and light level to the desired settings for operation DIAL ADJUSTMENTS Time Delay and Light Level control dials are located on the bottom of the sensor 1 Adjust Time Delay The time delay is the amount of time that elapses before lights turn off since the sen...

Страница 9: ...oon icon as desired this lowers the light level setting Remember the sensor must detect motion for lights to turn on The lights turn on later in the evening The lights turn off sooner in the morning Notes When testing adjustments make sure not to block any of the light that is reaching the sensor or reflect any light into the sensor s lens The sensor requires about 5 seconds for light level adjust...

Страница 10: ...ere is no movement in the coverage area the sensor should turn lights off low in 12 seconds Reset the time delay to the desired value 3 If the lights do not turn off low have a person qualified to check high voltage connections verify that the sensor and lighting are wired correctly see Wiring and Installation page 5 6 CAUTION Make sure power is turned off at the circuit breaker before checking wi...

Страница 11: ...120VAC 60Hz 270 Outdoor Indoor PIR Motion Sensor includes cover plate EWF 205 120 120VAC 60Hz 270 Outdoor PIR Motion Sensor includes two lamp holders and cover plate EW 200 277 277VAC 60Hz 270 Outdoor Indoor PIR Motion Sensor with Isolated Relay includes cover plate EW 205 277 277VAC 60Hz 270 Outdoor Indoor PIR Motion Sensor includes cover plate When ordering add W for Arctic White or G for Archit...

Страница 12: ...2800 De La Cruz Boulevard Santa Clara CA 95050 USA Technical Support 800 879 8585 www wattstopper com 00335r4 09 2014 Please Recycle ...

Отзывы: