Wattsonic AIO ESS | USER MANUAL
Danger: Do not connect the N-wire as a protective ground wire to the inverter casing.
Otherwise, it may cause electric shock.
Attention: Good grounding is good for resisting surge voltage shock and improving
EMI performance. Inverters must be well-grounded.
For a system with only one inverter, just ground the PE cable.
For a multi-inverter system, all inverters PE wire need to be connected to the same
grounding copper bar to ensure equipotential bonding.
Single inverter wiring diagram
This diagram is an example without special
requirement on electrical wiring connection.
Neutral line of AC supply can be isolated or
switched.
This diagram is an example for Australia and
New Zealand. Neutral line of AC supply must
not be isolated or switched.
Ground terminal connection steps:
1) The external grounding terminal is
located in the lower right side of the
inverter.
2) Fix the grounding terminal to the PE wire
with a proper tool and lock the grounding
terminal to the grounding hole in the lower
right side of the inverter.
External ground connection
Connect the inverter and ground
bar through PE wire to achieve the
purpose of grounding protection.
Please always remember wiring the
PE wire before wiring other wires.
PV
Array
Grid
Normal
Loads
RCD
RCD
Back-up
Loads
PV
Array
Communication
Communication
BACK-UP
The additional
grounding hole
ON-GRID
PV1+
Breaker
E-BAR
N-BAR
Breaker
RJ45
1(L1)
5(L1
-S1)
12(L)
9(L3-S1)
10(L3-S2)
2(L2)
6(L1
-S2)
3(L3)
7(L2-S1)
4(N)
8(L2-S2)
13(N)
Breaker
Main Switch/Breaker
CT
CT-1
CT-2
CT-3
Switch/Breaker
L1
L1
L2
L2
L3
L3
N
N
PV2+
PV1-
PV2-
RJ45-BMS
RJ45-Meter
B+
B-
Battery
Wattsonic
Hybrid
Inverter
Meter
PV
Array
Grid
Normal
Loads
RCD
RCD
Back-up
Loads
PV
Array
Communication
Communication
BACK-UP
The additional
grounding hole
ON-GRID
PV1+
Breaker
E-BAR
N-BAR
Breaker
RJ45
1(L1)
5(L1
-S1)
12(L)
9(L3-S1)
10(L3-S2)
2(L2)
6(L1
-S2)
3(L3)
7(L2-S1)
4(N)
8(L2-S2)
13(N)
Breaker
Main Switch/Breaker
CT
CT-1
CT-2
CT-3
Switch/Breaker
L1
L1
L2
L2
L3
L3
N
N
PV2+
PV1-
PV2-
RJ45-BMS
RJ45-Meter
B+
B-
Battery
Wattsonic
Hybrid
Inverter
Meter