Wattsonic AIO ESS | USER MANUAL
19
The Wattsonic WTS 6~12kW series is designed with IP65 protection for indoor and
outdoor installations. When selecting an inverter installation location, the following
factors should be considered:
The wall on which the inverter is mounted must be strong and can withstand the
weight of the inverter for a long time.
The inverter needs to be installed in a well-ventilated environment.
Do not expose the inverter directly to strong sunlight to prevent the power derating
due to excessive temperature.
The inverter should be installed in a place with shelter to prevent direct exposure to
sunlight and rain.
Install the inverter at the eye level for easy inspection of screen data and further
maintenance.
The ambient temperature of the inverter installation location should be between -30
°C and 60 °C.
The surface temperature of the inverter may reach up to 75 °C. To avoid risk of burns,
do not touch the inverter while it’s operating and inverter must be installed out of
reaching of children.
The area is completely water proof.
The floor is flat and level.
There are no flammable or explosive materials.
The ambient temperature is within the range from 0 to 50.
The temperature and humidity is maintained at a constant level.
There is minimal dust and dirt in the area.
The distance from heat source is more than 2 meters.
The distance from air outlet of whole system is more than 0.5 meters.
Do not cover or wrap the battery case or cabinet.
Do not place at a children or pet touchable area.
The installation area shall avoid of direct sunlight.
There is no mandatory ventilation requirements for battery module, but please avoid
of installation in confined area(minimum 300mm to top/left/right/front).
The aeration shall avoid of high salinity, humidity or temperature.
Mechanical Installation
Selection of Installation Location