4.5  Humidity detection input 

 

The product has a humidity detection input. 

possible types of signal: 

 

Water temperature sensor (CTN 10k

Ω

): Require 

BT-D03 RF RH thermostat 

 

A humidity contact sensor 

 

1. 

Humidity contact sensor 

Format of the signal  

The input is a free contact 

No Humidity 

Opened contact 

Humidity detected 

Closed contact 

 

In cooling mode, when humidity is detected, the 

controller: 

 

Stops the pump signal  if DIP7=ON  (Safety 

approach) 

 

Closes all actuators  if DIP7=ON  (Safety 

approach) 

 

Requests  the WFC HCM RF to enable the 

dehumidifier 

If the controller is a sub controller, the cooling demand 

is not sent to the main controller 

 

 

2. 

Water temperature sensor.  

For each zone, the controller computes the dew point 

based on the ambient temperature and relative 

humidity  sent by each thermostat.  When the water 

temperature reaches the dew point  in one zone, the 

controller 

 

Closes the actuator of the zone  if DIP7=ON 

 

Enables remote dehumidifier 

 

Requests  the WFC HCM RF to enable the 

dehumidifier 

If the controller is a sub controller, the cooling demand 

of the zone is not sent to the main controller 

 

  

 

 

4.6  NC/NO actuators 

 

Connect one NC or NO actuator per connector 

 

230V actuators for WFHC 06Z 02 HC RF 

230 and WFHC 10Z 02 HC RF 230 

 

24V actuators for WFHC 06Z 02 HC RF 

24 and WFHC 10Z 02 HC RF 24 

 

The type of actuators is defined by DIP2. 

It is necessary to use the same type for all actuators. 

 

 

 

 

 

 

 

 

 

 

 

Содержание WFHC 06Z 02 HC RF 24

Страница 1: ...1 Water Floor Controller Wireless Heating Cooling WFHC 06Z 02 HC RF 24 WFHC 06Z 02 HC RF 230 WFHC 10Z 02 HC RF 24 WFHC 10Z 02 HC RF 230...

Страница 2: ...2 USER GUIDE GB...

Страница 3: ...the installation complies with existing regulations before operation to ensure proper use of the installation 2 PRESENTATION The Connecting box WFC HC RF is especially designed to control your Under F...

Страница 4: ...ing mode Pump Drier Led Green Blue Red Fix Green Pump is triggered Red blinking System error security detection humidity sensor error Blue blinking Global humidity detection Blue flashing Humidity con...

Страница 5: ...C input DIP6 Anti Grip OFF Enabled See 7 1 ON Disabled DIP7 Humidity management OFF Comfort approach See 5 5 ON Safety approach DIP8 Humidity sensor OFF ON OFF sensor See 5 5 ON Pipe temperature sens...

Страница 6: ...central unit as an ON OFF device This solution allows getting a remote control of the H C mode from the application Format of the signal The input could be free contact or live contact 230V Mode Free...

Страница 7: ...ng demand and pump output stop is configurable Pump stops 5 minutes after heating or cooling demand stop if DIP switch 3 OFF Pump stops 20 minutes after heating or cooling demand stop if DIP switch 3...

Страница 8: ...d is not sent to the main controller 2 Water temperature sensor For each zone the controller computes the dew point based on the ambient temperature and relative humidity sent by each thermostat When...

Страница 9: ...ase you need to install the external antenna outside the metallic box Please respect the mounting to optimize sensitivity and avoid any dysfunction Antenna must be installed outside the metallic box i...

Страница 10: ...Thermostats Put product in RF pairung mode refer to corresponding instruction manual If RF pairing is done the leds of the channels selected on the WFHC 02 HC RF must turn Green and the thermostats m...

Страница 11: ...WFHC 02 HC RF returns to normal mode and the led on the repeater becomes green fix 5 1 2 Multiple controller s installation If there are multiple interconnected controllers in the installation there...

Страница 12: ...both WFC H C return to normal mode 5 2 System configuration with central unit The central unit centralizes the communication between controllers Device 1 WFC H C RF Device 2 BT CT02 RF Remarks By pres...

Страница 13: ...order to trigger a dehumidifier Device 1 WFHC 02 HC RF Device 2 BT WR02 RF or BT FR02 RF Remarks By pressing for 5 seconds the controller goes in RF pairing menu Bu using and select zone 4 Red led pr...

Страница 14: ...d or blue blinking on Heat and Cool led Security detection The contact of the security input is opened If you not using a security thermostat make sure you have installed a strap on the security therm...

Страница 15: ...ctrical protection Class II with functional earth IP Protection IP30 Shipping and storage temperature 10 C 50 C 14 F 122 F Power supply 230 Vac 10 50Hz Output maximum load 2 outputs Relay 5A Actuators...

Страница 16: ...C RF 24 and WFHC 10Z 02 HC RF 230 Weight xxxxxx 8 DIRECTIVES Designation Description Link Low Voltage Directive LVD The Low Voltage Directive LVD 2014 35 EU ensures that electrical equipment within ce...

Страница 17: ...tances Directive RoHS 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2011 65 EU Waste Electrical Electronic Equipment Directi...

Страница 18: ...leva Str P O Box 55 post office Trakia 4023 Plovdiv Bulgaria T 359 32 605 300 F 359 32 605 301 E mail info wattsindustries bg http wattswater eu Germany Austria and Switzerland Watts Industries Deutsc...

Отзывы: