background image

14 

 

 

6. 

Other Features 

6.1  Anti Grip Feature 

 

The feature is enable using DIP6 (See 4.3). If the valves 

are not active during a week, a complete exercise is 

triggered (ac pump Heat/cool demand 

sent to the WFHC HCM 02 RF 230). 

 

 

 

 

6.2  Reset 

In case of dysfunction, it may be required to reset the product to factory setting. By pressing simultaneously on 

 and 

 up to getting all zone LED in red,  the controller reset is triggered and the product restarts. 

 

 

 

 

 

Trouble shooting 

 

Trouble # 

Trouble 

Description 

Trouble shooting 

Red or blue 

blinking on Heat 

and Cool led 

Security detection 

The contact of the security input is opened 

If you not using a security 

thermostat, make sure you 

have installed a strap on the 

security thermostat input. 

Otherwise control the 

temperature of the pipe (too 

hot in heating mode, too cold 

in cooling mode) 

Red / Blue 

blinking on Heat 

and Cool led 

RF Issue 

The controller has lost the connection with 

a RF device other than a thermostat 

Check distance between 

devices. If the controller is 

installed within a metallic box, 

use an external antenna 

located outside the metallic 

box. 

Red 

blinking on 

Pump/Drier 

Led 

 

System error 

 

 

Blue flashing on 

Pump/Drier Led 

 

Humidity configuration problem 

 

Red fix on Data 

led 

USB error 

 

 

Содержание WFHC 06Z 02 HC RF 24

Страница 1: ...1 Water Floor Controller Wireless Heating Cooling WFHC 06Z 02 HC RF 24 WFHC 06Z 02 HC RF 230 WFHC 10Z 02 HC RF 24 WFHC 10Z 02 HC RF 230...

Страница 2: ...2 USER GUIDE GB...

Страница 3: ...the installation complies with existing regulations before operation to ensure proper use of the installation 2 PRESENTATION The Connecting box WFC HC RF is especially designed to control your Under F...

Страница 4: ...ing mode Pump Drier Led Green Blue Red Fix Green Pump is triggered Red blinking System error security detection humidity sensor error Blue blinking Global humidity detection Blue flashing Humidity con...

Страница 5: ...C input DIP6 Anti Grip OFF Enabled See 7 1 ON Disabled DIP7 Humidity management OFF Comfort approach See 5 5 ON Safety approach DIP8 Humidity sensor OFF ON OFF sensor See 5 5 ON Pipe temperature sens...

Страница 6: ...central unit as an ON OFF device This solution allows getting a remote control of the H C mode from the application Format of the signal The input could be free contact or live contact 230V Mode Free...

Страница 7: ...ng demand and pump output stop is configurable Pump stops 5 minutes after heating or cooling demand stop if DIP switch 3 OFF Pump stops 20 minutes after heating or cooling demand stop if DIP switch 3...

Страница 8: ...d is not sent to the main controller 2 Water temperature sensor For each zone the controller computes the dew point based on the ambient temperature and relative humidity sent by each thermostat When...

Страница 9: ...ase you need to install the external antenna outside the metallic box Please respect the mounting to optimize sensitivity and avoid any dysfunction Antenna must be installed outside the metallic box i...

Страница 10: ...Thermostats Put product in RF pairung mode refer to corresponding instruction manual If RF pairing is done the leds of the channels selected on the WFHC 02 HC RF must turn Green and the thermostats m...

Страница 11: ...WFHC 02 HC RF returns to normal mode and the led on the repeater becomes green fix 5 1 2 Multiple controller s installation If there are multiple interconnected controllers in the installation there...

Страница 12: ...both WFC H C return to normal mode 5 2 System configuration with central unit The central unit centralizes the communication between controllers Device 1 WFC H C RF Device 2 BT CT02 RF Remarks By pres...

Страница 13: ...order to trigger a dehumidifier Device 1 WFHC 02 HC RF Device 2 BT WR02 RF or BT FR02 RF Remarks By pressing for 5 seconds the controller goes in RF pairing menu Bu using and select zone 4 Red led pr...

Страница 14: ...d or blue blinking on Heat and Cool led Security detection The contact of the security input is opened If you not using a security thermostat make sure you have installed a strap on the security therm...

Страница 15: ...ctrical protection Class II with functional earth IP Protection IP30 Shipping and storage temperature 10 C 50 C 14 F 122 F Power supply 230 Vac 10 50Hz Output maximum load 2 outputs Relay 5A Actuators...

Страница 16: ...C RF 24 and WFHC 10Z 02 HC RF 230 Weight xxxxxx 8 DIRECTIVES Designation Description Link Low Voltage Directive LVD The Low Voltage Directive LVD 2014 35 EU ensures that electrical equipment within ce...

Страница 17: ...tances Directive RoHS 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2011 65 EU Waste Electrical Electronic Equipment Directi...

Страница 18: ...leva Str P O Box 55 post office Trakia 4023 Plovdiv Bulgaria T 359 32 605 300 F 359 32 605 301 E mail info wattsindustries bg http wattswater eu Germany Austria and Switzerland Watts Industries Deutsc...

Отзывы: