14
6.
Other Features
6.1 Anti Grip Feature
The feature is enable using DIP6 (See 4.3). If the valves
are not active during a week, a complete exercise is
triggered (ac pump Heat/cool demand
sent to the WFHC HCM 02 RF 230).
6.2 Reset
In case of dysfunction, it may be required to reset the product to factory setting. By pressing simultaneously on
,
and
up to getting all zone LED in red, the controller reset is triggered and the product restarts.
Trouble shooting
Trouble #
Trouble
Description
Trouble shooting
Red or blue
blinking on Heat
and Cool led
Security detection
The contact of the security input is opened
If you not using a security
thermostat, make sure you
have installed a strap on the
security thermostat input.
Otherwise control the
temperature of the pipe (too
hot in heating mode, too cold
in cooling mode)
Red / Blue
blinking on Heat
and Cool led
RF Issue
The controller has lost the connection with
a RF device other than a thermostat
Check distance between
devices. If the controller is
installed within a metallic box,
use an external antenna
located outside the metallic
box.
Red
blinking on
Pump/Drier
Led
System error
Blue flashing on
Pump/Drier Led
Humidity configuration problem
Red fix on Data
led
USB error