UK
ENGLISH
DSBA3003 • Rév. 07/07/2020
18
POWER SUPPLY AND CONTROL
N
Open Close
Ph
TP/PE
FC2
FC1
FCF
FCO
6
5
7
FEEDBACK
4
8
9
1
TLF
TL0
2
3
N Ph
10
11
H
F
C
A
B
C
D
M ~
230V
LS
VL
MR
RG
NR
BU
OG
BC
BC
D2
D1
SNAA950000
A1
A2
Rep. Designation
Rep. Designation
FCO Open limit switch
FCF Close limit switch
FC1 Auxiliary limit switch 1
FC2 Auxiliary limit switch 2
C Capacitor
F Motor thermoswitch
Rep. Designation
TLO Torque switch : opening
TLF Torque switch : closing
H Anti-condensation heater
M Motor
VL Purple
MR Brown
RG Red
NR Black
BU Blue
OG Orange
BC White
D1/D2
Failure report terminal (230V AC max / 5
A )
230V electric diagram
The terminal temperature can reach 90°C
The used wires must be rigid (feedback voltages: 4 to 250V AC/DC)