Rep.
Designation
A 24V DC terminal strip
B Block battery terminal strip
C
State feedback terminal strip
(load or battery failure)
D Green LED
E Red LED
Voltage 24V
DC
Rates current 0,8A
Maximal current 2,4A
Initial loading time 14h max.
Load state feedback
relay
24V DC - 1A
max
Temperature
-10°C to
+40°C
Color
Status
Red
Blinks/off/Blinks...
Battery disconnected or out of service
Green Off
Red
Blinks
Battery loading cycle in progress (max 14h)
Green On
Red
Off
Battery loading cycle finished
Green On
Red
Off
Actuator electrical supply during 3 minutes (failure mode)
Green Blinks
rapidly
Red
Blinks rapidly
Microcontroller failure
Green Off
Code
FAILSAFE: electronic board
FAILSAFE: led meaning