manualshive.com logo in svg
background image

Operating and Field Test Procedure 

The Watts No. TK-7 Backflow Preventer Test Kit is especially 

made to test the individual check modules of the Watts Series 7 

residential dual check backflow preventers and can also be used 

to test any double check valve backflow preventer, Series 709/

LF709 or 007/LF007. The test kit contains three segments of 

durable shatterproof tubing, two brass adaptors used to assem-

ble the three tubing segments, and test hardware to enable 

testing of Series 7 check modules and standard double checks. 

A rugged simulated leather carrying case is provided for ease of 

handling and compactness.

Specifications

•  Total working height of tube - 44"
•  Adaptors - (2) Brass, for Series 7 modules and double checks
•  Tubing - Three segments of plastic tubing
•  Moisture resistant instruction panel
•   Case - Durable simulated leather - weather proof and mildew 

proof

Case

Instruction  

Panel

Water Column 

Sight Tube

Adaptor for Testing 

Series 7 Modules

Adaptor for 

Testing Double 

Check Valve

NOTICE

Backflow prevention assemblies 

MUST

 be installed by a licensed 

journeyman tradesperson, who is recognized by the authority 

having jurisdiction, and inspected for compliance with local safety 

codes. Certified testing and maintenance are required to ensure 

proper function and maximum effectiveness of assemblies. These 

services must begin upon installation and be provided at intervals 

not to exceed one year and as system conditions warrant.

Instructions 
No. TK-7

Backflow Preventer Test Kit

No. 7 Check Modules

Complete valve cannot be tested in the 

line, however, each check module Part No. 

SA7B16 can be tested individually as follows:

Module Test Procedure

Purpose:

 To test check valves for tightness 

in the direction of flow.
Using Watts TK-7 test kit proceed as follows:
1.  Remove first check module from valve 

body and insert complete with O-ring in 

plug module adaptor. Seat firmly with mov-

ing portion of check module facing up.

2.  Assemble module adaptor hand tight to 

bottom half.

3.  Assemble 3 piece water column sight tube 

in numerical sequence and attach to top 

half of body module adaptor.

4.  Holding in vertical position, fill sight tube 

with water (no water leakage can be per-

mitted at sight tube joints).

5.  Observe liquid level. Liquid level may 

drop but as minimum water column of 28 

inches (1.0psi) (6.9 kPa) or greater should 

be maintained when the check module is 

operating correctly. If water column falls 

below 28 inches, check module is fouled 

and should be replaced (See assembly 

instructions).

6.  Remove first check module from module 

adaptor, and repeat above procedure with 

second check module.

Adaptor for Testing  

No. 7 Modules

Body Module 

Adaptor

O-ring

1st or 2nd 

Check Module

O-ring

Plug Module 

Adaptor

Double Check 

Adaptor

Threaded for 

Connection to 

Test Cocks

EZ-TC Adaptor

Adaptor for Testing  

Double Check Valves

Field Testing Procedure

IS-TK-7

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Отзывы: