Installation – Indoor Sensor 077

Sensor Testing 

Instructions

A good quality test meter 

capable of measuring up to 

5,000 kΩ (1 kΩ = 1000Ω) is 

required to measure the sen-

sor resistance. In addition to 

this, the actual temperature 

must be measured with either 

a good quality digital ther-

mometer, or if a thermometer 

is not available, a second 

sensor can be placed along-

side the one to be tested and 

the readings compared.
First measure the tempera-

ture using the thermometer 

and then measure the resis-

tance of the sensor at the 

control. The wires from the 

sensor must not be connect-

ed to the control while the 

test is performed. Using the 

chart on the following page, 

estimate the temperature 

measured by the sensor. 

The sensor and thermometer 

readings should be close. If 

the test meter reads a very 

high resistance, there may be 

a broken wire, a poor wiring 

connection or a defective 

sensor. If the resistance is 

very low, the wiring may be 

shorted, there may be mois-

ture in the sensor or the sen-

sor may be defective. To test 

for a defective sensor, mea-

sure the resistance directly at 

the sensor location.
Do not apply voltage to a 

sensor at any time as dam-

age to the sensor may result.

Содержание Tekmar 077

Страница 1: ...ermistor mount ed on a white enamel steel plate to provide an accurate measurement of the indoor temperature The 077 can be mounted flush onto a stan dard duplex electrical box Wiring enters from the...

Страница 2: ...5 STEP 4 Installing the Sensor Front Cover 5 Sensor Testing Instructions 6 Resistance Table 6 Technical Data 7 Limited Warranty and Remedies 8 WARNING Read this Manual BEFORE using this equipment Fai...

Страница 3: ...inor or moderate injury Identifies practices actions or failure to act which could result in prop erty damage or damage to the equipment Learn how to properly and safely use the equipment BEFORE insta...

Страница 4: ...One Indoor Sensor 077 One Installation Manual 077_D Two 6 32 x 1 screws Choose a Location The Indoor Sensor should be installed on an interior wall of the desired zone to be controlled Do not mount t...

Страница 5: ...sources of electromagnetic noise shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit If using shielded cable one end of the shield wire should be connecte...

Страница 6: ...and then measure the resis tance of the sensor at the control The wires from the sensor must not be connect ed to the control while the test is performed Using the chart on the following page estimate...

Страница 7: ...g baked enamel white on steel Dimensions 41 2 H x 27 8 W x 1 2 D 114 x 73 x 13 mm 3 16 D 5 mm when installed Operating range Splash proof 60 to 140 F 50 to 60 C Sensor NTC thermistor 10 k 77 F 25 C 0...

Страница 8: ...he defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s agreement and warranty with its customers Any representations or warra...

Отзывы: