REVERSE OSMOSIS 

 

INSTALLATION AND OPERATION MANUAL 

 

 

R12-Wall Mount 

Содержание R12-0150

Страница 1: ...REVERSE OSMOSIS INSTALLATION AND OPERATION MANUAL R12 Wall Mount...

Страница 2: ......

Страница 3: ...end user Successful long term performance of an RO system depends on proper operation and maintenance of the system This includes the initial system startup and operational startups and shutdowns Pre...

Страница 4: ...nt II Controls Indicators and Components III Operation A Installation B Plumbing Connections C Electrical D Startup E Control Function F Operation and Maintenance Log G Troubleshooting IV Replacement...

Страница 5: ...ufficient to eliminate chemicals that would attack the membrane materials A SPECIFICATIONS R12 0150 R12 0250 R12 0600 R12 1200 Maximum Productivity Gallons per day 150 250 600 1200 Quality membrane re...

Страница 6: ...uspended solids sediment from the feed water Backwashing the media removes the trapped particles Backwash can be initiated by time or differential pressure Water Softener Used to remove calcium and ma...

Страница 7: ...nd temperature dependent Silica fouling can be prevented with chemical injection and or reduction in recovery I CONTROLS INDICATORS and COMPONENTS see figure 1 A On Off Switch Turns the unit on and of...

Страница 8: ...Figure 1...

Страница 9: ...ter line should never be restricted Membrane and or system damage may occur if the product line is blocked 3 Connect the reject water outlet to a drain The reject outlet is located at the reject needl...

Страница 10: ...d 200 psi on the pump discharge gauge Figure 1 item F 10 Allow the product water to flow to drain for 30 minutes 11 Turn off the system and connect the product line to the point of use The product wat...

Страница 11: ...ED WATER TEMP FEED WATER HARDNESS FEED WATER CHLORINE LEVEL PRE FILTER INLET PRESSURE PRE FILTER OUTLET PRESSURE REMARKS Note Change the prefilter when the differential pressure increases by 5 10 psi...

Страница 12: ...and reject Slime in pipes and vessels Shock dosage of sodium bisulfite Continuous feed of low conc bisulfite at reduced pH Peracetic acid sterilization Clean with alkaline anionic surfactant Chlorine...

Страница 13: ...of common replacement parts is provided below Contact your dealer for replacement parts assistance Part Number Description S9550 D T Pre filter housing 10 R9677 SV2514 1 RO membrane pressure vessel 2...

Страница 14: ...the new membranes 6 Lightly lubricate the brine seals on the new membranes with clean water 7 Install the new membranes in the direction of flow with the brine seal end going in last 8 Lightly lubrica...

Страница 15: ...ture Correction Factors Deg C Deg F Correction Factor 30 86 1 16 29 84 2 1 13 28 82 4 1 09 27 80 6 1 06 26 78 8 1 03 25 77 1 00 24 75 2 0 97 23 73 4 0 94 22 71 6 0 92 21 69 8 0 89 20 68 0 86 19 66 2 0...