Lync WQ-AS
SECTION 3: OPERATION
L- OMM-007_A
•
5/6/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
14
of
42
WARNING!
Do not attempt to remove the cartridge filter lid without relieving pressure. To open lid, close
shutoff valves before and after filter, press pressure relief button to relieve pressure. Once
pressure has been relieved, remove eyebolts and lid. To start up filter, replace lid, tighten
eyebolts, and open shutoff valves slowly to check for leaks. If lid O-ring does not seat
properly, close shutoff valves, relieve pressure, open lid, apply a small amount of non-
petroleum based lubricant to the O-ring to help it seal, reposition O-ring and close lid.
Fill in install date and rebed due date on product label located on the front of each tank as a
reminder to replace AquaSolve media every 3 years. The system is now ready for service.
3.6.
Lync UV Controller
The Lync UV controller features are:
•
Automatic lamp dimming for cooler operation
•
Flow switch
•
Lamp out audible alarm
•
Glow cap lamp indicator
•
Graphic touch screen display to show key operational data
•
Alarm output for solenoid valve
•
UV sensor input
•
4-20 milliamp output for UV Intensity (when UV Sensor is used).
3.6.1. Lync UV Controller Wiring
Figure 3-2 UV Controller
4-20mA Transmitter (Left is
'Loop +', Right is 'Loop -')
Future Accessories
Top Cat 5- Future Accessories
Bottom Cat 5- UV Sensor
Alarm Relay A (Left to Right)
Normally Closed/Common/
Normally Open
Alarm Relay B (Left to Right)
Normally Closed/Common/
Normally Open
Power Input AC 100-240 VAC
50/60HZ
Right- Ground to Chassis
Center- Flow Switch
Left- Antenna Wire