Troubleshooting
Problem:
Solution:
Outlet temperature above set point
1. Ensure flow is above the minimum rated flow by opening the hot water valve on two to four fixtures
being supplied with tempered water from the panel.
2. Ensure that the cold supply isolation valve is in the fully open position as shown below.
3. On the Home Screen, check the “Cold Supply Temp” using the icon (see below) to cycle through
the various fields. Ensure that it is lower than the set point temperature and that the cold supply line has
no obstructions or closed valves restricting flow to the IntelliStation.
4. Reset the control by opening and closing the circuit breaker switch and wait 60 seconds to resume normal
operation.
Closed (OFF)
Open (ON)
!
Always use proper precautions when accessing circuit breaker box.
Mixed Outlet Setpoint
140°F
50°F
Cold Supply Temp
PRGM
Recirc Pump OFF