Troubleshooting Guide 

Series LF1170-M2 and LFL1170-M2

Period Inspection/Maintenance

This valve requires periodic inspection and verification of the out-

let temperature by a licensed contractor. Corrosive water condi-

tions, hot inlet water temperature over 200°F (93°C), unauthor-

ized adjustments or repairs could render the valve ineffective for 

its intended service. Regular cleaning and checking of thermo-

stat assembly helps to maximize valve life and mixing function. 

Frequency of cleaning depends on local water conditions.

Pressure — Temperature

Minimum Supply Pressure (Static):

 30psi (207 kPa)

Inlet Temperatures:

  hot inlet, 120°F – 200°F (49°C – 93°C),  

cold inlet, 40°F – 85°F (4°C – 29°C)

Hot Water Inlet to Outlet Differential Temperature:

 5°F (3°C)

LF1170-M2 Temperature Out: 

     Field range: 90°F – 160°F (32°C – 71°C), adjustable. 

Accurate within ±3°F (1.7°C)

LFL1170-M2 Temperature Out: 

  

  Field range: 60°F – 120°F (16°C – 49°C), adjustable.  

Accurate within ±3°F (1.7°C)

Maximum Temperature:

 200°F (93°C)

Maximum Pressure:

 150psi (10.3 bar)

Maximum Pressure Differential Between Hot and Cold 

Water Supplies:

 25%.

Approval: CSA B125 certified 

Listing: ASSE 1017 and IAPMO UPC

Symptom

Cause

Solution

Unable to reach required set point or set 
point difficult to set

1.  Supply temperatures not within specified 

limits

 
2.  Hot and cold supplies reversed
 
3.  Filters are blocked by debris

1.  Check differential temperature between hot 

and cold supplies and outlet 10°F (5.6°C) 
minimum required

2. Reinstall valve with supplies connected to 

marked inlets

3. Clean filters

Unable to achieve required flow

1. Too much pressure drop at fixture 
 
 
2.  Checks valve/filters blocked by debris

1.  Measure supply pressures and check 

against flow chart. Look for restrictions in 
valve or piping

2.  Clean check valves/filters

Valve does not maintain required temper-
ature or temperature changes over time

1. Fluctuation in supply pressures
 
2.  Check valve/filters blocked by debris
3.  Recirculation loop not piped properly

1.  Stabilize water pressures with pressure 

regulating or balancing valves

2.  Clean check valves/filters
3.  Pipe recirculated tempered water return so 

it connects to hot water source and cold 
side of mixing valve  (see Product Guide for 
piping details)

Discharge temperature too hot or cold

1. Valve not calibrated properly

1.  Readjust valve temperature per installation 

instructions

Hot water from cold water tap or cold 
from hot

1. Check valves fouled

1. Clean check valves/filters

Valve is noisy

1. Water velocity is too high
2.  Valve not sized properly

1.  Reduce water velocity with pressure  

regulating valves

2.  Check flow required versus rated flow 

capacity of valve

No flow from valve

1.  Hot or cold water supply failure or shutoffs 

closed 

2.  Check valve/filters blocked by debris

1.  Open shutoffs or restore hot and cold sup-

ply 

2.  Clean check valves and filters

Flow from valve fluctuates

1.  Fluctuation in supply pressures
2.  Check valve/filters blocked by debris

1.  Stabilize water pressure with pressure regu-

lating valves

2.  Clean check valves and filters

Содержание LF1170 Series

Страница 1: ...amage or damage to the equipment Keep this Manual for future reference WARNING Use caution when soldering Protect yourself and others FUMES AND GASES can be hazardous to your health HEAT RAYS INFRARED RADIATION from flame or hot metal can injure eyes WARNING You are required to consult the local building and plumbing codes prior to installation If the information in this manual is not consistent w...

Страница 2: ...To decrease temperature turn clockwise 4 Lower handle and tighten screw 5 Check outlet temperature Quick Connect Installation 1 Mark pipe as shown This is pipe insertion depth 2 Clean pipe end 1 Remove collet clip 2 Depress collet 3 Pull tubing from tailpiece 3 If using PEX tubing insert pipe stiffener provided into end of pipe 4 Push tubing into tailpiece up to mark 5 Insert collet clip To Connec...

Страница 3: ... outlet 10 F 5 6 C minimum required 2 Reinstall valve with supplies connected to marked inlets 3 Clean filters Unable to achieve required flow 1 Too much pressure drop at fixture 2 Checks valve filters blocked by debris 1 Measure supply pressures and check against flow chart Look for restrictions in valve or piping 2 Clean check valves filters Valve does not maintain required temper ature or tempe...

Страница 4: ...h is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplication improper installation or improper maintenance or alteration of ...

Отзывы: