9
PROGRAMMING MODE continued
Level III Cycle Programming - C Values
Several Level III program parameters can be adjusted to
fine-tune valve operation for non-standard applications.
Typically these parameters will not need to be adjusted as
the default settings accommodate most applications. Contact
your Water Treatment Professional before attempting any
programming. The parameters are accessible by pressing and
holding the UP and SET buttons until the display shows a “C”
value.
NOTE: The controller must be in the treated water position
to change settings.
C#
Description
Range
Minimum
Increments
Default Setting
Notes
C1*
Brine Draw
0-200
1 Min
See Notes
Automatically calculated from resin volume
and salt dosage settings and draw rate.
C2
Slow Rinse
0-200
See Notes
Initial time automatically calculated to provide
two bed volumes of rinse.
C3
Standard Backwash
0-20
7
Flow rate dictated by size of drain line flow
controller.
C4
Standard Fast Rinse
0-200
3
Rinses residual regenerant from tank.
C5*
Refill
0-200
See Notes
Automatically calculated from resin volume
and salt dosage settings and refill rate.
C13
Cleaning Backwash
0-200
14
Control uses C13 in place of C3 when the
number of standard regenerations is more than
or equal to the cleaning cycle interval P19.
C14
Cleaning Fast Rinse
0-200
6
Control uses C14 in place of C4 when the
number of standard regenerations is more than
or equal to the cleaning cycle interval P19.
*Cannot be changed in Level III Cycle Programming.
Содержание IOM-WQ-PROSENSE
Страница 20: ...20 PROBE KIT Item No QTY Part No Description 1 1 30212618 Probe Cable Clips Kit 1...
Страница 23: ...23 ProSense METER FLOW DATA...
Страница 24: ...24 ProSense INJECTOR FLOW DATA 1600 SERIES INJECTORS...
Страница 25: ...25 PROSENSE CONTROL VALVE DIMENSIONS...
Страница 27: ...27 Slow Rinse Position Rapid Rinse Position Brine Tank Fill Position WATER CONDITIONER FLOW DIAGRAMS continued...
Страница 29: ...29 SERVICE ASSEMBLIES continued...