Check local codes for installation requirements.  Pipe lines should 

be thoroughly flushed to remove foreign material before installing 

the unit.  A strainer should be installed as shown, ahead of backflow 

preventer to prevent disc from unnecessary fouling.  Install valve in 

the line with arrow on valve body pointing in the direction of flow.

For indoor installations, it is important that the valve be easily 

accessible to facilitate testing and servicing.  Do not install in a 

concealed location.

CAUTION:  

Do not install with strainer when backflow preventer is used on 

seldom-used water lines which are called upon during emer-

gencies, such as fire sprinkler lines, etc.

It is important that Series 719 and LF719 be tested periodically 

in compliance with local codes but at least once a year or more 

often depending upon system conditions.  Regular inspection, 

testing and cleaning assures maximum life and proper product 

function.

NOTE:

  Fire Protection System Installations

The National Fire Protection Agency (NFPA) Guidelines require 

a confirming flow test to be conducted whenever a “main line” 

valve such as the shutoff valves or a backflow assembly have 

been operated.  Certified testers of backflow assemblies must 

conduct this test.  The trim valves of the confirming flow test 

must be closed during the test.  When the test is completed, 

the trim valves must be returned to a fully open position.

Outside - 

Figure 2

Parallel - 

Figure 3

Where approved by code, Watts recommends a custom engi-

neered Watts PVS Series water supply valve station consisting of 

two or more 719 and LF719 Series valves piped in parallel to serve 

a larger supply main. This type of installation is employed whenever 

it is required to maintain water flow to a facility. Typical applications 

include hospitals, multi-family dwellings, malls and other similar 

applications.

A properly designed Watts PVS valve station provides redundant 

flow paths, a continuous supply of adequate water, testing and 

servicing of an individual valve without supply interruption, and 

long service life.

The size, quantities and design of parallel valve installations should 

be exactly in accordance with the engineer’s judgment and the 

published Best Practice Guide of Watts Regulator wherever pos-

sible. For a copy of the Watts Best Practice Guide, call Watts at 

1-800-617-3274. 

2

Installation Instructions

Series 719 and LF719 Double Check Valve Assemblies

719AQT

Meter Box Installation

First Shutoff 

Valve

719QT-S Vertical flow-up installation

Strainer

Min. 12"

Fiberglass WattsBox

Now Available, WattsBox Insulated Enclosures.

For more information, send for ES-WB or ES-WB-T.

Figure 2

719QT-S

First 

Shutoff Valve

Figure 3

First 

Shutoff Valve

719QT-S

Strainer

Figure 1

Содержание Golden Eagle 719 Series

Страница 1: ...e per year or more as service conditions warrant Corrosive water conditions and or unauthorized adjustments or repair could render the product ineffective for the service in tended Regular checking and cleaning of the product s internal components helps assure maximum life and proper product function RP IS 719 NOTE For Australia and New Zealand Pipeline strainers should be installed between the up...

Страница 2: ... of the confirming flow test must be closed during the test When the test is completed the trim valves must be returned to a fully open position Outside Figure 2 Parallel Figure 3 Where approved by code Watts recommends a custom engi neered Watts PVS Series water supply valve station consisting of two or more 719 and LF719 Series valves piped in parallel to serve a larger supply main This type of ...

Страница 3: ...FREE Repair Kits 1 2 2 15 50mm When ordering specify ordering code number kit number and valve size Ordering code Kit No Size in mm Total Repair Kits 0889083 RK 719 T 1 2 15mm 0889084 RK 719 T 3 4 20mm 0889085 RK 719 T 1 25mm 0889086 RK 719 T 11 4 11 2 32 40mm 0889087 RK 719 T 2 50mm Kit consists of 2 First or Second Check Repair Kits 1st or 2nd Check Kits 0888100 RK 719R10 CK4 1 2 3 4 15 20mm 088...

Страница 4: ...Company has no control This warranty shall be invalidated by any abuse misuse misapplication improper installation or improper maintenance or alteration of the product Some States do not allow limitations on how long an implied warranty lasts and some States do not allow the exclusion or limitation of incidental or consequential damages Therefore the above limitations may not apply to you This Lim...

Отзывы: