Instructions for Installing FS-200-W

General Purpose Liquid Flow Switch

Sizes: 1" – 6" 

The Watts 

FS-200-W Flow Switch

 is used to start or stop elec-

trically operated equipment such as burners, pumps or alarms 

by detecting liquid flow through piping. It is designed for use in 

water media applications and is not intended for use in hazard-

ous or corrosive fluids.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Flow Switch Location

The preferred installation of the FS-200-W is in a horizontal pipe with a straight run of 

at least 5 pipe diameters on each side of the paddle 

(Figure 1)

. There should be no 

restrictions from elbows, valves, orifices, etc. Refer to Table 1 below for flow rates.

The Flow Switch can be installed in a vertical pipe 

only if the flow direction of 

the liquid is upward.

 Table 1 does not apply to vertical installations.

WARNING

!

Electrical shock hazard. To prevent electrical shock, 

death or equipment damage, disconnect power supply 

before installing or servicing control.

Local building or plumbing codes may require modifica-

tions to the information provided.  You are required to  

consult the local building and plumbing codes prior 

to installation.  If the information provided here is not 

consistent with local building or plumbing codes, the 

local codes should be followed.  This product must be 

installed by a licensed contractor in accordance with 

local codes and ordinances.

WARNING

!

CAUTION

!

•  To prevent serious burns, boiler should be thoroughly cooled 

before installing or servicing control.

•  The FS-200-W is designed as an operating control. It is the 

responsibility of the installer to provide safety or limit control on 

installations where an operating control failure would result in 

personal injury and/or property loss.

•  The FS-200-W is not intended for use in explosive environments.

FIGURE 1

Dimensions

TABLE 1 FLOW SPECIFICATIONS 

 

 

PIPE SIzE   

1" 

1

1

4

" 1

1

2

"  2" 2

1

2

"

 

3" 

  

FLOW

 

INCREASES 

4.5  8.1 11.8  16.5  25  33  51  85

120

*

 

  

FLOW DECREASES 

2.2  6.8 7.6  9.3  19  22 38  75

*

 100

*

 

  

FLOW

 

INCREASES

 

14.8  22.1 25.7  32.3  75  90

*

 110

*

 170

*

 240

*

  

FLOW DECREASES

 

13.8  20.1 23.7  30.5  72  85

*

 100

*

 155

*

 220

*

*Calculated for various pipe sizes. Flow rates may vary ±10% from values above.

MINIMuM

ADJuSTMENT
MAxIMuM

ADJuSTMENT

4"

5"

6"

Содержание FS-200-W

Страница 1: ...th or equipment damage disconnect power supply before installing or servicing control Local building or plumbing codes may require modifica tions to the information provided You are required to consult the local building and plumbing codes prior to installation If the information provided here is not consistent with local building or plumbing codes the local codes should be followed This product m...

Страница 2: ...66 Fax 978 975 8350 Watts com Canada Tel 905 332 4090 Fax 905 332 7068 Watts ca Latin America Tel 52 81 1001 8600 Fax 52 81 8000 7091 Watts com A Watts Water Technologies Company Pressure Temperature Maximum Service Pressure 160 psi Maximum Temperature 250 F Enclosure NEMA type 1 for indoor use only Formed sheet metal construction Powder coated cover zinc plated chassis brass body Not for use in h...

Страница 3: ...ue décès ou endommagement de l équipement débranchez le bloc d alimentation avant l installation ou l entretien de la commande Les codes du bâtiment ou de plomberie locaux peuvent commander des modifications à l information fournie Vous êtes tenu de consulter les codes du bâtiment ou de plomberie locaux avant l installation Si les informations fournies ne sont pas compatibles avec les codes du bât...

Страница 4: ...e utilisation intérieure uniquement Construction en métal en feuille profilé Châssis en acier poudré et galvanisé corps en laiton Ne pas utiliser dans des zones dangereuses Contacts contacteur SPDT Régime de fonctionnement du moteur 7 4 FLA 44 4 LRA à 120 V c a Régime de fonctionnement asservi 125 V à 120 240 V c a Plage de temp ambiante 0 C à 80 C 32 F à 176 F Plage de temp du support 0 C à 121 C...

Отзывы: