If the update was successful, the system restarts using the new version, in this case 
v1.16:
 

If the update failed, the system restarts with the existing version v1.03.
If there is a problem, it is always possible to restore the “factory” version as follows: 

1.

  Check  that  the  microSD  card  is  in  its  slot  (the  card  itself  is  required,  but  no  other 

special files are required).

2.

 Hold the 3      ,      and       keys simultaneously and power up the system.

Caution: wait until the factory reset has started before releasing the keys. 

Following an update, the program file should ideally be removed from the SD card.

Manual Adjustment of the mixed water temperature 

(in the event of power failure)

This function is used to manually set the required temperature in the event of a power 
failure.
Remove the electric actuator, disconnect probe C (red) from the actuator and replace the 
white cap (included with the e-Cartridge) on the e-Cartridge rod so the water tempera-
ture can be adjusted as required.

Note that even without electrical power, the e-ULTRAMIX

®

 thermostat system continues 

to mix the water to the set temperature.

Replacing the e-Cartridge

Opening the mixing valve:

- Close the cold water, hot water and mixed water valves.
- Remove the actuator and the mixed water probe from the e-Cartridge.
- Remove the e-Cartridge.

Replacing the e-Cartridge:

- Fit the new e-Cartridge.
- Fit the temperature probe to the new e-Cartridge.

To enable automatic notification of the next scheduled replacement, remember to reset 
the alert 

(see Settings menu “Cartridge alert")

.

v1.16

26

ENGLISH

EN

Содержание e-ultramix Series

Страница 1: ...ation Installation and Operation Manual Manuale di Installazione e Uso Installatie en bedieningshandleiding wattswater eu FR NL UK IT FR NL UK IT FR NL UK IT FR NL UK IT NL Manuel d installation Instr...

Страница 2: ...l eau mitig e Programmation de cycles de choc thermique Historique Menu param tre 1 Date heure 2 Contraste 3 Langues 4 Unit s 5 Export SD 6 Alerte cartouche 7 Menu param trage Calibration Test des re...

Страница 3: ...ULTRAMIX assurez vous d avoir lu et compris les instructions d taill es dans ce fascicule Vous rencontrez ce symbole lors de la lecture de ce manuel celui ci est pr sent afin d attirer votre attention...

Страница 4: ...37ELEC e ULTRAMIX 2 22TX96E37ELEC Gamme pour nouvelle installation pour mise niveau d un mitigeur ULTRAMIX existant 3 56 l mn 3 80 l mn 3 120 l mn 5 175 l mn 5 260 l mn 6 400 l mn 3 56 l mn 3 80 l mn...

Страница 5: ...rotection IP 20 Pouvoir de coupure Pour les relais chasse circulateur production E C S 10 A 250 VAC NO Pour le relais alarme 8 A 250 VAC NO NC Conformit CE oui Maintien de l heure pendant 24 heures en...

Страница 6: ...m D mm E mm F mm G P total 117 120 81 117 120 81 144 142 96 182 160 108 218 200 129 242 217 144 126 19 98 126 19 98 133 23 116 149 24 145 164 36 175 173 36 198 G 3 4 2 06 kg G 3 4 2 06 kg G 1 3 06 kg...

Страница 7: ...FR FRAN AIS Centrale de programmation P 320 g 86 mm 160 mm 50 5 mm 145 5 mm 3 mm 3 mm e Cartouche Kit de rin age livr uniquement avec e ULTRAMIX 7 FRAN AIS FR...

Страница 8: ...e peut tre programm e via la centrale par pas de 1 C Traitement thermique pr ventif l horloge int gr e la centrale de l e ULTRAMIX permet de programmer sur le circuit d eau des cycles de traitement t...

Страница 9: ...cement pour vis de fixation Bornier alimentation Installation de la centrale de programmation e ULTRAMIX La centrale de programmation e ultramix peut tre install e directement sur une base solide par...

Страница 10: ...ue Historique Menu param tres 1 Calibration 2 Test des relais 3 Cycle forc 4 Chasse forc e 5 T choc thermique 6 Limitation T 7 Dur e de chasse 8 Modbus 9 Code 10 Mise jour 11 Config Usine Menu Param t...

Страница 11: ...u mitig e AVEC BOUCLAGE T T M T T M T M CENTRALE DE PROGRAMMATION Production ou arriv e Retour de bouclage eau mitig e Relais de chasse Sortie ModBus interfacer avec GTB Relais d alarme Liaison filair...

Страница 12: ...es techniques nonc s pages 5 et 6 Le diam tre nominal du mitigeur doit tre identique au diam tre des tubes d alimentation ainsi qu celui du d part en eau mitig e le d calage d une section imm diatemen...

Страница 13: ...e tuyau cf sch ma hydraulique page 11 l aide d un ruban adh sif alu Option sans branchement de la sonde D la sonde d eau mitig e E vert est prise en compte pour la validation du choc thermique Raccord...

Страница 14: ...ais production eau chaude 10 A 250 VAC NO SYST ME PRODUCTION E C S Le c blage du relais de production d eau chaude est n cessaire pour envoyer la consigne de temp rature au syst me E C S A E B C D Sch...

Страница 15: ...omme indiqu par la fl che sur le produit Cartouche anti br lure pour douche Cartouche anti br lure pour lavabo Cartouches anti br lure D signation R f rence Cartouche anti br lure MF 1 2 douche 229715...

Страница 16: ...cran revient sur l cran d accueil Appuyer une fois sur la touche afin de faire appara tre les 5 pictogrammes en bas de l cran R glage de la temp rature de l eau mitig e Pour ce r glage il est imp rati...

Страница 17: ...mp rature soient adap t s aux r glementations locales ou nationales cf Menu Param trage T choc thermique Historique L historique vous permet de visualiser les infos relatives aux cycles de choc thermi...

Страница 18: ...atiques soient valid es il est primordial que la carte micro SD soit positionn e dans son emplacement d di Le nouveau fichier sauvegard annule et remplace le pr c dent L e ULTRAMIX conserve une ann e...

Страница 19: ...lisation et calibrer la sonde de temp ra ture d eau mitig e directement sur la centrale par rapport la temp rature mesur e avec le thermom tre de r f rence Test des relais utiliser lors de l installat...

Страница 20: ...ou nationales applicables une modification doit tre effectu e en s lectionnant ce menu Le choc thermique est consid r e r ussie d s l obtention d une des 3 combinaisons dur e temp rature d finies ou...

Страница 21: ...de l installation Pour information le ModBus est configur en mode RTU la vitesse de communication tant de 19 200 Bauds Code Il est possible de prot ger l acc s la centrale e ULTRAMIX celle ci ne l tan...

Страница 22: ...tance via un syst me de Gestion Technique du B timent par l interface RS485 de la centrale Le protocole de communication utilis est le ModBus Le bornier de connexion est accessible sur le c t de la ce...

Страница 23: ...ction corrective L eau ne coule pas la bonne temp rature V rifier qu il y a de l eau aux arriv es que les tuyauteries sont bien raccord es La mise au point de la temp rature a t elle t effectu e corre...

Страница 24: ...rant l appareil Mise jour du logiciel interne via la carte micro SD La mise jour s effectue via la carte micro SD et les versions actualis es seront mises disposition sur notre site internet Les fichi...

Страница 25: ...giciel et de l actionneur Pour commencer la mise jour cocher la case Oui avec le curseur et valider par Si la carte SD ou le fichier de mise jour ne sont pas pr sents ou bien si la version du logiciel...

Страница 26: ...n vous permet en cas de coupure lectrique d assurer le r glage manuel de la temp rature souhait e Pour cela d monter l actionneur lectrique d brancher la sonde C rouge de l action neur et remettre en...

Страница 27: ...Il est constat que le mitigeur fonctionne correctement comme d fini par des normes 3 L chec du mitigeur est d en partie ou en totalit une installation d fectueuse du syst me d eau chaude duquel le mi...

Страница 28: ...s o vous n auriez pas la possibilit de flasher ceux ci connectez vous notre site www wattswater fr et consultez notre vid oth que e ULTRAMIX TUTORIEL D INSTALLATION FR FRAN AIS WATTS INDUSTRIES France...

Страница 29: ...FRAN AIS FR...

Страница 30: ...temperature Programming thermal shock cycles Data history Settings menu Date and time Contrast Languages Units SD export Cartridge alert Configuration menu Calibration Test relays Forced cycle Forced...

Страница 31: ...the detailed instructions in this booklet This symbol attracts the reader s attention and highlights critically important instructions that must be followed WITHOUT FAIL to avoid damage to the system...

Страница 32: ...2TX95E37ELEC e ULTRAMIX 2 22TX96E37ELEC Product range for new systems for upgrading an existing ULTRAMIX unit 3 56 L min 3 80 L min 3 120 L min 5 175 L min 5 260 L min 6 400 L min 3 56 L min 3 80 L mi...

Страница 33: ...king capacity for relays flush circulation pump DHW production 10 A 250 VAC NO for alarm relay 8 A 250 VAC NO NC CE compliant yes Retains time setting for 24 hours in the event of power supply failure...

Страница 34: ...mm D mm E mm F mm G Total weight 117 120 81 117 120 81 144 142 96 182 160 108 218 200 129 242 217 144 126 19 98 126 19 98 133 23 116 149 24 145 164 36 175 173 36 198 G 3 4 2 06 kg G 3 4 2 06 kg G 1 3...

Страница 35: ...UK ENGLISH Programming control unit Weight 320 g 86 mm 160 mm 50 5 mm 145 5 mm 3 mm 3 mm e Cartridge Flushing kit included with e ULTRAMIX only 7 ENGLISH EN...

Страница 36: ...splayed on the control unit screen The setpoint temperature for mixed water can be configured via the control unit in increments of 1 C Preventive heat treatment the integrated timer in the e ULTRAMIX...

Страница 37: ...g screws and plugs fixings not included fig 4b Fix the control unit to a flat surface wall etc If the programming control unit is fitted with cables for connecting relays etc please take care not to c...

Страница 38: ...ettings menu 1 Calibration 2 Relay Test 3 Forced cycle 4 Forced flushing 5 Thermal shock T 6 T limitation 7 Flushing time 8 Modbus 9 Password 10 Update 11 Factory reset Parameters 2 Contrast 3 Languag...

Страница 39: ...mixed water operation WITHOUT RECIRCULATION LOOP Example of normal mixed water operation WITH RECIRCULATION LOOP T T M T T M T M Production or inlet Mixed water loop return Flush relay Cold water 55...

Страница 40: ...technical characteristics pages 5 and 6 The nominal diameter of the mixing valve must be identical to the supply pipe diameter and mixed water outlet pipe diameter using the next size up or down is ac...

Страница 41: ...unit and position the external probe on the pipe see pipe layout diagram on page 11 using aluminium tape Optional if probe D is not connected the mixed water probe F is used to monitor thermal shock...

Страница 42: ...standard wiring diagram Hot water production relay 10 A 250 VAC NO DHW PRODUCTION SYSTEM Hot water production relay wiring is necessary to send temperature data to the DHW system A E B C D ModBus conn...

Страница 43: ...vice Anti scald cartridge for shower Anti scald cartridge for washbasin Anti scald cartridges Description Part number Anti scald cartridge M F 1 2 shower 2297155 Anti scald cartridge M 24x1 with aerat...

Страница 44: ...er 2 minutes the display reverts to the Home screen Press the key once to display the 5 icons at the bottom of the screen Setting the mixed water temperature For this setting it is imperative to simul...

Страница 45: ...ation menu Thermal shock T Data history The Data history screen allows you to view information about the thermal shock cycles Using the and keys select the day then confirm using Details of the therma...

Страница 46: ...to ensure the microSD card is correctly inserted in the slot provided The new backup file deletes and replaces the previous file The e ULTRAMIX stores a year s worth of data information about thermal...

Страница 47: ...rate the mixed water temperature probe directly on the control unit with reference to the value measured using the reference thermometer Test relays For use during installation or maintenance Activate...

Страница 48: ...rmal shock is considered successful when it reaches one of the 3 defined temperature duration combinations and maintains this combination to the end of the programmed time Forced cycle Launch a Therm...

Страница 49: ...t the Modbus is configured in RTU mode with a communication rate of 19 200 baud Password Access to the e ULTRAMIX control unit can be protected by defining a 4 digit security password this option is n...

Страница 50: ...Manage ment System via the control unit s RS485 interface using the Modbus communication protocol The connection terminal block is located on the side of the programming control unit The Modbus addre...

Страница 51: ...at the right temperature Check that there is water on both inlets that the piping is connected Has the temperature setting been completed correctly The mixed water is flowing but not enough Hot or col...

Страница 52: ...e low point drain valve or by opening the device Updating the built in software via the microSD card Updates are performed via the microSD card and newer software versions are made available on our we...

Страница 53: ...ctuator software versions are displayed To start the update check the Yes box using the cursor and validate using If the SD card or update file are not present or the software version is older than th...

Страница 54: ...e This function is used to manually set the required temperature in the event of a power failure Remove the electric actuator disconnect probe C red from the actuator and replace the white cap include...

Страница 55: ...orrectly as defined by standards 3 The failure of the mixing valve is partially or fully due to a defective installation of the hot water system of which the mixing valve is a part 4 The mixing valve...

Страница 56: ...de please visit our website www wattswater co uk and check out our video library e ULTRAMIX INSTALLATION TUTORIAL UK ENGLISH Watts Industries UK Ltd Colmworth Business Park PE19 8YX St Neots United Ki...

Страница 57: ......

Страница 58: ...Programmazione dei cicli di disinfezione termica Storico dei dati Menu parametri Data e ora Contrasto Lingua Unit Esportazione su scheda micro SD Allarme cartucce Menu parametri Taratura Prova dei re...

Страница 59: ...istruzioni descritte in modo dettagliato nel presente manuale Questo simbolo utilizzato nel presente manuale per attirare l attenzione dell utente sulle prescrizioni di sicurezza che OBBLIGATORIO risp...

Страница 60: ...nuovi impianti per ammodernamento di impianti esistenti gi dotati di miscelatore ULTRAMIX 3 56 l min 3 80 l min 3 120 l min 5 175 l min 5 260 l min 6 400 l min 3 56 l min 3 80 l min 3 120 l min 5 175...

Страница 61: ...A per il rel di allarme 8 A 250V CA NA NC Conformit CE s Mantenimento dell impostazione dell ora per 24 ore in caso di interruzione dell alimenta zione elettrica Programmi e regolazioni dell utente sa...

Страница 62: ...C mm D mm E mm F mm G P 117 120 81 117 120 81 144 142 96 182 160 108 218 200 129 242 217 144 126 19 98 126 19 98 133 23 116 149 24 145 164 36 175 173 36 198 G 3 4 2 06 kg G 3 4 2 06 kg G 1 3 06 kg G 1...

Страница 63: ...Unit di programmazione P 320 g 86 mm 160 mm 50 5 mm 145 5 mm 3 mm 3 mm e Cartuccia Kit di risciacquo fornito esclusivamente con e ULTRAMIX IT ITALIANO 7 ITALIANO IT...

Страница 64: ...nit Il valore di setpoint della temperatura dell acqua miscelata pu essere programmato a partire dall unit con incrementi di 1 C Disinfezione termica preventiva l orologio integrato nell unit centrale...

Страница 65: ...della sonda di allacciamento Connettore Modbus Lettore micro scheda SD Connettore attuatore elettrico Morsettiera rel del sistema di circolazione Morsettiera rel di allarme Morsettiera rel di scarico...

Страница 66: ...ne dei cicli di disinfezione termica Storico dei dati Menu parametri 1 Calibrazione 2 Relay test 3 Ciclo forzato 4 Scarico forzato 5 T disinfezione 6 Limite T 7 Durata scarico 8 Modbus 9 Password 10 U...

Страница 67: ...5 C VM1 A VM VM1 B VM valvole micrometriche per la stabilizzazione della temperatura di circuito VM1 A apertura tra 70 e il 90 VM1 B apertura tra 30 e il 10 50 C Esempio di applicazione in cui il volu...

Страница 68: ...etro nominale del miscelatore deve essere identico al diametro dei tubi di alimen tazione e al diametro del tubo di mandata dell acqua miscelata tollerato uno scarto di una sezione immediatamente supe...

Страница 69: ...izzando un nastro adesivo in alluminio Opzione se non viene effettuato il collegamento della sonda D la sonda dell acqua miscelata E verde viene utilizzata anche per la convalida della disinfezione te...

Страница 70: ...el di produzione di acqua calda 10 A 250 VAC NO SISTEMA DI PRODUZIONE DI ACQUA CALDA SANITARIA Il cablaggio del rel di produzione di acqua calda necessario per poter inviare il valore di setpoint dell...

Страница 71: ...riportata sul prodotto Protezione antiscottatura per doccia Protezione antiscottatura per lavabo Protezioni antiscottatura Descrizione Codice Protezione antiscottatura MF 1 2 doccia 2297155 Protezion...

Страница 72: ...ipale Premere una volta il tasto per visualizzare i 5 pittogrammi in basso sullo schermo Regolazione della temperatura dell acqua miscelata Per effettuare questa regolazione necessario fare scorrere l...

Страница 73: ...ocali o nazionali v Menu dei Parametri T di disinfezione termica Storico dei dati Lo storico dei dati permette di visualizzare le informazioni relative ai cicli di disinfezione termica Utilizzando i t...

Страница 74: ...ffinch queste esportazioni manuali o automatiche vengano convalidate necessario che la scheda micro SD sia posizionata nell apposito alloggiamento Il nuovo file salvato annulla e sostituisce il preced...

Страница 75: ...di configurazione Fare scorrere l acqua alla normale temperatura di utilizzo e tarare la sonda della tempe ratura dell acqua miscelata direttamente sull unit centrale rispetto alla temperatura misurat...

Страница 76: ...a ai sensi delle normative locali o nazionali applicabili per effettuare eventuali modifiche necessario selezionare questo menu La disinfezione termica viene considerata riuscita all otteni mento di u...

Страница 77: ...sto indirizzo sia univoco sulla rete Si segnala che il ModBus configurato in modalit RTU e la velocit di comunicazione di 19 200 baud Password possibile proteggere l accesso all unit e ULTRAMIX define...

Страница 78: ...ma di Building Management System usando l interfaccia RS485 dell unit centrale Il protocollo di comunicazione utilizzato il ModBus La morsettiera accessibile sul lato dell unit di programmazione La co...

Страница 79: ...rettiva L acqua non scorre alla giusta temperatura Verificare che vi sia la giusta portata di acqua e che i tubi siano collegati correttamente La regolazione della temperatura stata effettuata corrett...

Страница 80: ...l software interno con scheda micro SD L aggiornamento viene eseguito attraverso la scheda micro SD e le versioni aggiornate saranno messe a disposizione sul nostro sito web I file di aggiornamento no...

Страница 81: ...li del software e dell attuatore Per avviare l aggiornamento spuntare la casella S con il cursore e confermare con il tasto Se la scheda SD o il file di aggiornamento non sono presenti o se la version...

Страница 82: ...garantire la regolazione manuale della temperatura desiderata Per fare ci smontare l attuatore elettrico scollegare la sonda C rossa dall attuatore e riposizionare il coperchio bianco fornito con la c...

Страница 83: ...stato constatato che il miscelatore funziona correttamente in conformit con le norme applicabili 3 Il guasto del miscelatore dovuto in toto o in parte a un installazione difettosa del sistema di produ...

Страница 84: ...e del sistema e ULTRAMIX Nel caso in cui non siate in grado di leggere questi codici potete accedere direttamente ai video dal nostro sito www wattswater it e ULTRAMIX TUTORIAL DI INSTALLAZIONE Watts...

Страница 85: ......

Страница 86: ...len Programmeren van de desinfectiecycli Log Parameters Datum en tijd Contrast Talen Eenheden SD Export Wissel binnenwerk Parameter menu Calibratie Relaistest Geforceerde cyclus Geforceerd spuien Desi...

Страница 87: ...nstallatie inbedrijfstelling of onderhoud van het e ULTRAMIX systeem U ziet dit symbool bij het lezen van deze handleiding dit is om uw aandacht te vestigen op instructies die u ABSOLUUT moet naleven...

Страница 88: ...ELEC e ULTRAMIX 2 22TX96E37ELEC Productoverzicht voor een nieuwe installatie voor het upgraden van een bestaande ULTRAMIX mengkraan 3 56 l mn 3 80 l mn 3 120 l mn 5 175 l mn 5 260 l mn 6 400 l mn 3 56...

Страница 89: ...hakelvermogen Voor de relais spoelen circulatiepomp SWW productie enz 10 A 250 VAC NO Voor het alarmrelais 8 A 250 VAC NO NC CE conformiteit ja Houdt 24 uur lang de tijd bij in het geval van een stroo...

Страница 90: ...E mm F mm G Totaalgewicht 117 120 81 117 120 81 144 142 96 182 160 108 218 200 129 242 217 144 126 19 98 126 19 98 133 23 116 149 24 145 164 36 175 173 36 198 G 3 4 2 06 kg G 3 4 2 06 kg G 1 3 06 kg G...

Страница 91: ...Bedieningseenheid Gew 320 g 86 mm 160 mm 50 5 mm 145 5 mm 3 mm 3 mm e Patroon Spoelkit uitsluitend geleverd bij de e ULTRAMIX NL NEDERLANDS 7 NEDERLANDS NL...

Страница 92: ...er kan op de bedieningseenheid in stappen van 1 C worden geprogrammeerd Preventieve desinfectie De ingebouwde klok van de bedieningseenheid van de e UL TRAMIX maakt het mogelijk om preventief thermisc...

Страница 93: ...het deksel vooraan fig 4c terug na het maken van de elektrische aansluitingen Installatie van de e ULTRAMIX bedieningseenheid De e ultramix bedieningseenheid kan direct op een stevig oppervlak bijv ee...

Страница 94: ...emp 7 Spuiduur 8 ModBus 9 Password 10 Updaten 11 Fabrieksinstell Parameter menu 6 Begrenzing t 7 Spuiduur 8 Modbus 9 Password 10 Updaten 11 Fabrieksinstell Parameters 2 Contrast 3 Talen 4 Eenheden 5 S...

Страница 95: ...water Koud water 39 C Voorbeeld van een normale werking met mengwater ZONDER RECIRCULATIE Voorbeeld van een normale werking met mengwater MET RECIRCULATIE T T M T T M T M Productie of invoer Retour re...

Страница 96: ...e nominale diameter van de mengkraan moet gelijk zijn aan de diameter van de toevoerleidingen alsook de uitgaande leidingen mengwater een verschil in diameter bij het hogere of lagere gedeelte wordt g...

Страница 97: ...schema pagina 11 met aluminiumtape Optioneel als de sonde D niet wordt gebruikt wordt rekening gehouden met de sonde E groen voor het gemengde water om de thermische desinfectie te bevestigen Aanslui...

Страница 98: ...Relais warmwater productie 10 A 250 VAC NO SWW SYSTEEM De bedrading van het relais voor warmwaterproductie is nodig om de gewenste temperatuur naar het SWW systeem te sturen A E B C D Elektrisch sche...

Страница 99: ...t product Anti verbrandingspatroon voor de douche Anti verbrandingspatroon voor de wastafel Beveiliging tegen verbranden Omschrijving Referentie Anti verbrandingspatroon MF 1 2 douche 2297155 Anti ver...

Страница 100: ...tscherm Druk eenmaal op de toets om de 5 pictogrammen onderaan het scherm zichtbaar te maken Mengtemperatuur instellen Voor deze instelling laat u het water uit de tappunten stromen zoals bij normaal...

Страница 101: ...infectie tijd temperatuur worden aangepast aan lokale of nationale regelgeving zie Menu Instellingen T desinfectie Log In de log kunt u info met betrekking tot desinfectiecycli zichtbaar maken Selecte...

Страница 102: ...tig of automatisch daadwerkelijk plaatsvinden is het belangrijk dat de micro SD kaart in zijn speciale sleuf is geplaatst Het nieuwe bestand dat wordt opgeslagen vervangt het voorafgaande De e ULTRAMI...

Страница 103: ...Instellingen Laat het water op de normale gebruikstemperatuur lopen en kalibreer de temperatuur sonde voor mengwater rechtstreeks op de eenheid in vergelijking met de gemeten temperatuur met de refere...

Страница 104: ...onale regelgeving wijzigingen worden via dit menu worden doorgevoerd Desinfectie wordt beschouwd succesvol te zijn vanaf het moment dat een van de 3 vastgestelde combina ties van tijd temperatuur is b...

Страница 105: ...matie de ModBus is ingesteld in RTU mo dus en heeft een communicatiesnelheid van 19 200 baud Password De toegang tot de bedieningseenheid e ULTRAMIX kan worden beveiligd niet standaard ingesteld door...

Страница 106: ...an de eenheid op afstand de e ULTRAMIX besturen en informatie ophalen Het gebruikte communicatieprotocol is ModBus Het klemmenblok voor de aansluitingen is toegankelijk via de zijkant van de bedie nin...

Страница 107: ...elding Correctie Het water stroomt niet op de juiste temperatuur Controleer of er water is bij de aanvoerpunten warm en koud of de leidingen Is het instellen van de temperatuur goed verlopen Er is men...

Страница 108: ...n van de software via de micro SD kaart Het updaten wordt uitgevoerd via de micro SD kaart en bijgewerkte versies worden op onze website geplaatst zodra ze beschikbaar zijn De ge pdate bestanden moete...

Страница 109: ...Om het updaten te starten vinkt u het vakje Ja aan met de cursor en bevestigt u met Als de SD kaart of het updatebestand niet aanwezig is of wanneer de softwareversie ouder is dan de versie die al is...

Страница 110: ...in geval van een stroomstoring de gewenste temperatuur verze keren via een manuele instelling Hiervoor verwijdert u de elektrische actuator ontkoppelt u de sonde C rood van de actuator en plaatst u d...

Страница 111: ...ngkraan te demonteren of te forceren 2 Indien is gebleken dat de mengkraan juist werkt zoals bepaald in de normen 3 Het geheel of gedeeltelijk falen van de mengkraan het gevolg is van een defecte inst...

Страница 112: ...ien u de codes niet kunt scannen kunt u onze website www wattswater nl bezoeken en onze video s daar raadplegen e ULTRAMIX INSTALLATIEHANDLEIDING Watts Industries Belgium B V B A Beernemsteenweg 77A 8...

Отзывы: