Kit Components

The sensor connection kit includes the following four components. If any item is missing, speak with 

your account representative.

Requirements

•  #2 Phillips screwdriver 
•  Polytetrafluoroethylene (PTFE) tape (optional)
•  Instrument with small tip to change DIP switch settings
•  Power source, ranging from 12V to 24V
•  Wire stripper

A.  Flood sensor with male 2" NPT connection

The connection kit is suitable for installation on a metal air gap 

or pipe fitting with 2" female NPT connection.

NOTICE

B.  Sensor activation module with an 8' 4-conductor electrical 

cable, ground wire, and 4 attachment screws

C.  24V DC power adapter (requires a 120VAC, 60Hz,  

GFI-protected electrical outlet)

Содержание BMS

Страница 1: ...and triggers real time notification of potential flood conditions through the building management system or BMS Use of the SentryPlus Alert technology does not replace the need to comply with all req...

Страница 2: ...2 Contents Kit Components 3 Requirements 3 Install the Flood Sensor 4 Mount the Sensor Activation Module 5 Connect the Module Cable to the BMS Controller 7...

Страница 3: ...ith small tip to change DIP switch settings Power source ranging from 12V to 24V Wire stripper A Flood sensor with male 2 NPT connection The connection kit is suitable for installation on a metal air...

Страница 4: ...flood sensor to the air gap with a 2 female NPT connection 3 Twist on the sensor until it is flush with the air gap Hand tighten the sensor up to 15 ft lb Do not overtighten Install the Flood Sensor A...

Страница 5: ...charge is detected If the discharge meets the conditions of a qualifying event the normally open contact is closed to provide a signal to the BMS input terminal The wet threshold value must be set to...

Страница 6: ...ected to a power supply 4 Reattach the cover with the four screws making sure the O ring inside the cover is properly seated to maintain a seal 5 Remove the dust cover from the flood sensor 6 Remove t...

Страница 7: ...on the BMS controller NOTICE To use the optional 24V DC power adapter Distinguish the positive wire from the negative one The positive wire has white stripes and must be inserted into the power termin...

Страница 8: ...cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign ma...

Отзывы: