Installing Second Dual-action Check Module

1.   Insert second check module (A) into access port (B) with second 

check towers (C) pointing downstream. Push second check module 

(A) downstream into valve sealing ring (D) until check O-ring (E) rests 

against valve sealing ring (D). Push second check module (A) into its 

fully seated position by hand.

2.   Alternatively place 2"x4" piece of wood cut to 5" length (F) against 

the backside of the second check seat ring (G). Using a 1"x4" piece 

of wood cut to 16" length (H) as a lever between access port wall 

the 2"x4" (F) gently coax the second check module (A) into its fully 

seated position.

3.   Be certain second check module (A) is fully seated and check O-ring 

(E) is NOT “fish mouthed” or damaged.

4.   Tighten the second check retaining screws (I) 

ONLY AFTER 

the 

first

 check module as been installed.

The second check module must be fully seated to ensure 

retainer screws do not bind against check seat. Binding 

retainer screws against check seat will result in permanent 

damage to second check modules.

WARNING

!

FLOW

C

E

A

B

Not Binding

Binding

I

Installing First Dual-action Check Module

1.   Insert first check module (A) into access port (B) with first 

check towers (C) pointing downstream. Push first check 

module (A) upstream into valve sealing ring (D) until check 

O-ring (E) is resting against valve sealing ring (D). Without 

using excessive force, push first check module (A) into its 

fully seated position by hand.

2.   Alternatively, using a piece of 1"x4" wood cut to 16" length 

(F) as a lever between the second check seat (G) and the 

first check towers (C), push the first check module (A) into  

its fully seated position.

3.   Be certain first check module (A) is fully seated and check 

O-ring (E) is NOT “fish mouthed” or damaged.

4.   Now fully tighten the first and second check retaining screws (I).

The first check module must be fully seated to ensure 

retainer screws do not bind against check towers. Binding 

retainer screws against check towers will result in permanent 

damage to first check modules.

WARNING

!

FLOW

Not Binding

Binding

C

A

B

E

F

G

D

I

G

H

F

D

Содержание AMES Deringer 20G

Страница 1: ...equired to consult the local building and plumbing codes prior to installation If the information in this manual is not consistent with local building or plumbing codes the local codes should be follo...

Страница 2: ...tenance NOTE valve is still under pressure When opening test cocks water will be released Take precautions to ensure discharging water does not damage the surrounding area equipment or create an unsaf...

Страница 3: ...first check module flange C gently push the first check module in the downstream direction until the first check module can easily be removed from the access port by hand A A 1 Use a 11 8 socket wrenc...

Страница 4: ...A 2 Remove disk retaining washer B 3 Use a flathead screwdriver to remove the gasket from poppet cavity C 4 Install new red silicone poppet disk D 5 Reverse the order of the above instructions to rea...

Страница 5: ...the order of the above instructions to reassemble check Elastomer disk must be flat in clapper H cavity before tightening disk retainer screws F Do not cross thread disk retaining screws F F G D H B C...

Страница 6: ...t bind against check seat Binding retainer screws against check seat will result in permanent damage to second check modules WARNING FLOW C E A B Not Binding Binding I Installing First Dual action Che...

Страница 7: ...g from one side of the valve to the other A B F C E G D Close Test Cocks and Double Check All Closing Sealing Mechanisms 1 Using the test cock wrench or a small adjustable wrench close main test cocks...

Страница 8: ...st of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign mater...