Standard Components
Operation
The Rate-of-Flow Control ACV with Solenoid (On-Off) Feature is
designed to automatically limit flow rate to a constant, adjustable,
maximum, and open, allowing flow control action, or close drip-
tight as commanded by the Solenoid Pilot. It is controlled by a
normally open, differential control pilot designed to: 1) Open (allow-
ing fluid out of the main valve cover chamber) when the differential
pressure across the orifice plate is below its adjustable set point,
and, 2) Close (allowing fluid to fill the main valve cover chamber)
when the differential pressure across the orifice plate is above its
adjustable set point. A decrease in differential pressure causes the
valve to modulate towards an open position, increasing flow rate.
An increase in differential pressure causes the valve to modulate
towards a closed position, decreasing flow rate.
The Solenoid Pilot will either open to allow regulating action, or
close the valve drip-tight when energized. Specify energize to open
or close the Main Valve and voltage PRIOR to ordering.
The Orifice Plate Assembly should be installed three to five pipe
diameters downstream of the Rate-of-Flow Valve, and field con-
nected with
3/8
" minimum copper tubing in accordance with factory
piping schematic.
Please specify desired flow rate PRIOR to ordering.
1
X
X
X
Y/FC
Scale Percent:
161.997%
P/L
4
5
2
3
CLOSES VALVE
OPENS VALVE
FLOW
(AOS)
1 - Main Valve (905GD – Single Chamber)
2 - Rate-of-Flow Control
3 - 2-Way Solenoid
4 - Adjustable Closing Speed
5 - Orifice Plate Assembly
X - Isolation Cocks
1. Prior to installation, flush line to remove debris.
2. Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position
Indicator can be installed to provide visual indication of valve position and operation without disassembly.
3. Install isolation valves upstream and downstream of the main valve.
4. Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing
valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizon-
tal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to order-
ing if valve is to be installed other than horizontally in-line.
5. If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit
from damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and
replaced exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.
6. To accurately set flow rates, either a differential gauge or a flow meter should be installed.
7. Check orifice plate to assure that sense holes are free from obstruction.
8. Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.
9. After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.
Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to
adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system
from damaging over-pressure.
Installation
950GD-15 (Globe) Rate-of-Flow Control Valve with Solenoid
On-Off
2 IOM-A-ACV-950-15_650-15 2115
EDP# 1917072
© 2021 Watts