APPENDIX B – STARTUP, STATUS AND FAULT MESSAGES
OMM-0120_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
139
of
174
GF-128-I
Phone: 800-526-0288
11/15/2016
Table B-2. Fault Messages – Continued
FAULT MESSAGE
FAULT DESCRIPTION
OUTDOOR TEMP
SENSOR FAULT
The temperature measured by the Outdoor Air Sensor is out
of range.
OUTLET TEMP
SENSOR FAULT
The temperature measured by the Outlet Sensor is out of
range:
OUTLET TEMPERATURE display = SHt Indicates sensor is
shorted
OUTLET TEMPERATURE display = OPn indicates sensor is
open-circuited
PRG SWITCH CLOSED
DURING IGNITION
The Purge Position Limit switch on the Air/Fuel Valve closed
during ignition.
PRG SWITCH OPEN
DURING PURGE
The Purge Position Limit switch on the Air/Fuel Valve opened
during purge.
RECIRC PUMP
FAILURE
Internal Recirculation Pump has failed.
REMOTE SETPT
SIGNAL FAULT
The Remote Setpoint signal is not present or is out of range.
RESIDUAL
FLAME
The Flame signal was seen for more than 60 seconds during
standby.
SSOV
SWITCH OPEN
The SSOV switch opened during standby.
SSOV FAULT
DURING PURGE
The SSOV switch opened during purge.
SSOV FAULT
DURING IGN
The SSOV switch closed or failed to open during ignition.
SSOV FAULT
DURING RUN
The SSOV switch closed for more than 15 seconds during
Run.
SSOV RELAY
FAILURE
A failure has been detected in one of the relays that control
the SSOV.
STEPPER MOTOR
FAILURE
The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.
WARNING EXHAUST
TEMP HIGH (Flashing)
The exhaust gas sensor is measuring high temperature.
Level #1: 180ºF (82.2°C), Flash WARNING
Level #2: 190ºF (87.8°C), Govern fire rate/flash WARNING
Level #3. 200ºF (93.3°C), Shut down unit (requires manual
reset)