Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 4
– INITIAL START-UP
OMM-0137_J
• 12/20/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
50
of
167
PROPANE Combustion Calibration Instructions
16. With the valve position still at 100%, insert the combustion analyzer probe into the exhaust
manifold probe opening (see Figure 4-2a
– 4-2c in Section 4.2.3) and allow enough time
for the combustion analyzer reading to stabilize
17.
Compare the combustion analyzer’s oxygen (O
2
) reading to the
O
2
value in the
Reading
column (Figure 4-9). If they differ, go to the
Main Menu
→
Calibration
→
Input/Output
→
O2 Sensor
screen and adjust the
O2 Offset
parameter, up to
±3%
, to make the on-board
O
2
sensor match the value from the combustion analyzer. If your combustion analyzer is
correctly calibrated, and the on-board O
2
sensor cannot be made to match the analyzer,
the sensor may be defective and need to be replaced.
18. Compare the
O
2
value in the
Target
and
Reading
columns.
If they don’t match, adjust the
Blower Voltage
until the
O
2
value in both
columns
match; use either the
+
or
–
controls, or
press on the field and type the value directly.
19. If adjusting the blower voltage is not sufficient to get the
O
2
Reading
column to match the
Target
column, then repeat Step 15 to adjust the gas pressure up or down within the range
shown in the table, then repeat Step 18. Continue repeating Steps 15 and 18 until the gas
pressure is within the range in Table 4-4 and the
O
2
Reading
column to matches the
Target
column.
20.
Enter the downstream manometer’s gas pressure reading in the
Downstream Gas
Pressure
field. Note, this field appears only when
Valve Position %
=
100%
.
21. Compare the measured nitrogen oxide (NOx) and carbon monoxide (CO) readings to the
Target
values in the Table 4-5 (shown as a reference only)
. If you are not in a “NOx-
limited” area and/or do not have a NOx measurement in your analyzer, set the O
2
to the
value in the
Oxygen (O
2
) %
column in the table below.
TABLE 4-5: PROPANE Calibration Readings at 100% Valve Position
Model
Oxygen (O
2
) %
Nitrogen Oxide (NOx)
Carbon Monoxide (CO)
750 & 1000
5.5% ± 0.2%
≤100 ppm
<150 ppm
1500
5.2% ± 0.2%
≤100 ppm
<150 ppm
2000
6.0% ± 0.2%
≤100 ppm
<150 ppm
2500
5.0% ± 0.2%
≤100 ppm
<150 ppm
3000
5.2% ± 0.2%
≤100 ppm
<150 ppm
4000
4.5% ± 0.2%
≤100 ppm
<150 ppm
5000N
4.5% ± 0.2%
≤100 ppm
<150 ppm
5000
5.5% ± 0.5%
≤100 ppm
<150 ppm
6000
5.0% ± 0.5%
≤100 ppm
<150 ppm
NOTE:
These instructions assume that the
inlet air temperature is between 50°F and 100°F (10°C
– 37.8°C)
. If NOx readings exceed the target values in Table 4-4, above, or Table 4-6, below,
increase the O
2
level up to 1% higher than the Target value. You must then record the
increased O
2
value on the Combustion Calibration sheet.
22. On Benchmark 3000 - 6000 units
only
, record the manifold (downstream) gas pressure at
100%. This value will be used in Section 5.2.2:
Low Pressure Gas Test
, and Section 5.3.2:
High Pressure Gas Test
.
23. Once the O
2
level is within the specified range at 100%: