Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 3 - START SEQUENCE
OMM-0137_J
• 12/20/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
25
of
167
TABLE 3-2c: BMK750/1000 DUAL FUEL Air/Fuel Valve Position
–
NATURAL GAS
Air/Fuel Valve
Position (%
Open)
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
BMK750 Dual Fuel
BMK 1000 Dual Fuel
BMK750
Dual Fuel
BMK 1000
Dual Fuel
18% (Stop Level)
48,850 (14.3 Kw)
48,850 (14.3 Kw)
6.5%
4.9%
20%
62,000 (18.2 Kw)
62,000 (18.2 Kw)
8.3%
6.2%
30%
132,000 (38.7 Kw)
132,000 (38.7 Kw)
17.6%
13.2%
40%
239,000 (70.0 Kw)
239,000 (70.0 Kw)
31.9%
23.9%
50%
358,000 (104.9 Kw)
358,000 (104.9 Kw)
47.7%
35.8%
60%
488,300 (143.1 Kw)
488,300 (143.1 Kw)
65.1%
48.8%
70%
571,000 (167.3 Kw)
633,500 (185.7 Kw)
76.1%
63.4%
80%
633,500 (185.7 Kw)
756,000 (221.6 Kw)
84.5%
75.6%
90%
693,200 (203.2 Kw)
894,000 (262.0 Kw)
92.4%
89.4%
100%
750,000 (219.8 Kw)
1,000,000 (293.1 Kw)
100.0%
100.0%
TABLE 3-2d: BMK750/1000 DUAL FUEL Air/Fuel Valve Position
–
PROPANE GAS
Air/Fuel Valve
Position (%
Open)
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
BMK750 Dual Fuel
BMK 1000 Dual Fuel
BMK750
Dual Fuel
BMK 1000
Dual Fuel
18% (Stop Level)
48,850
(14.32
Kw)
48,850
(14.32 Kw)
7.1%
5.3%
20%
62,000
(18.2
Kw)
62,000
(18.2 Kw)
8.7%
6.5%
30%
132,000
(38.7
Kw)
132,000
(38.7 Kw)
16.7%
12.5%
40%
239,000
(70.0
Kw)
239,000
(70.0 Kw)
30.8%
23.1%
50%
358,000
(104.9
Kw)
358,000
(104.9 Kw)
44.9%
33.6%
60%
488,300
(143.1
Kw)
488,300
(143.1 Kw)
63.6%
47.7%
70%
571,000
(167.3
Kw)
633,500
(185.7 Kw)
72.7%
60.9%
80%
633,500
(185.7
Kw)
756,000
(221.6 Kw)
81.1%
71.0%
90%
693,200
(203.2
Kw)
894,000
(262.0 Kw)
85.7%
88.8%
100%
750,000
(219.8
Kw) 1,000,000 (293.1 Kw)
100.0%
100.0%