Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-
0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
93
of
153
7.3.3 Option 3 Outdoor Reset: Direct Wired Header Temp Sensor &
Direct Wired Outdoor Temp Sensor
OPTION 3
Instructions: Outdoor Reset, Direct Wired Header Temp Sensor & Outdoor Temp
Sensor
NOTE:
Both
Header Temp Sensor
and
Outdoor Temp Sensor
must be wired. See the
Edge
Controller Manual
(OMM-0139, GF-213) for more information.
Step 1: DIRECT WIRED
HEADER TEMP SENSOR WIRING
– BST MANAGER Unit
1. On the
BST Manager
unit, connect the
Header Temp Sensor
to the I/O board terminal
strip
J3
, terminals
4
(
Supply
)
and
5
(
Supply Header
-).
2. Connect the shield to any
Shield
terminal, such as terminal
3
or
8
on strip
J3
.
NOTES:
•
The
Header Temp Sensor
must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant’s supply water header.
•
Shielded pair 18 - 22 AWG cable is recommended for
Header Temp Sensor
wiring.
There is no polarity to be observed. The ground for the shield is at the
Shield
terminal
on the I/O the board. The sensor end of the shield must be left free and ungrounded.
Step 2: DIRECT WIRED
OUTDOOR TEMP SENSOR WIRING
– BST MANAGER Unit
1. On the
BST Manager
unit, connect the
Outdoor Temp Sensor
to the I/O board terminal
strip
J3
, terminals
1
(
Outside Temp
+
)
and
2
(
Outside Temp
-).
2. Connect the shield to any
Shield
terminal, such as terminal
3
or
8
on strip
J3
.
NOTES:
•
Twisted shielded pair 18 - 22 AWG cable is recommended for
Header Temp Sensor
wiring. There is no polarity to be observed. The sensor end of the shield must be left
free and ungrounded.
•
The
Outdoor Temp Sensor must
be mounted on the
North side of the building
where an average outside air temperature is expected. The sensor must be shielded
from direct sunlight as well as impingement by the elements. The
Outdoor Temp
Sensor
may be wired up to 200 feet (61m) from the boiler.
OUTDOOR TEMP SENSOR
I/O BOARD, STRIP J3
HEADER TEMP SENSOR
5 Supply Header-
3 Shield
I/O BOARD STRIP J3
4 Supply
2 Outside Temp -
3 Shield
1 Outside Temp +