Benchmark Platinum-Edge [II]: Operation-Service Manual
SECTION 7
– BOILER SEQUENCING TECHNOLOGY
OMM-
0137_E • GF-211 • 12/13/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
92
of
153
OPTION 2
Instructions: Constant Setpoint, Modbus Wired Header Temp Sensor
Step 2: OPTION 2 CONFIGURATION
On All Boilers:
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
:
•
Set the
Unit Mode
parameter to
BST Client
.
2. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Communication
:
•
Set the
Unit Address
parameter to the communication address of the unit.
On the BST Manager
only:
1. Go to
Main Menu
→
Advanced Setup
→
BST Cascade
, set the Parameters to the Values
in each menu in the table below.
Menu/Screen Name
Parameters
Values
Cascade
Configuration
Unit Mode
BST Manager
Hdr Temp Sensor
Header Temp
Sensor
Comm Address
240
Hdr Temp Point
14
Application
Configuration
Application
Space Heating
SH Operating Mode
Constant Setpoint
Outdoor Temp Sensor
Outdoor Sensor
Plant Setpoint
Header temperature required for the cascade
Cascade
Communication
Min Address
The
minimum
unit address in the cascade
Max Address
The
maximum
unit address in the cascade
Cascade Baud Rate
The baud rate for the cascade.