Test Procedure for Reduced
Pressure Zone Backflow Preventers

The following Test Procedure is one of several that is recognized
throughout the United States for verification of the functioning of
backflow preventers.
The following procedure is not a specific recommendation. The
Watts series of test kits are capable of performing any of the recog-
nized backflow test procedures.
A.  Open TC #4 and flush test cocks Nos. 1, 2, and 3 on BF 

assembly, then close TC #4.

B.  Turn tester on (before connecting hoses). Tester must read all 

zeros. Close VA and VB.

Test No. 1 - Relief Valve

1. Install high side hose between TC #2 and tester connection A.
2. Install low side hose between TC #3 and tester connection B.
3. Open VB then TC #3. Now open VA then TC #2 slowly. Close

VA then VB.

4. Close #2 shutoff valve.
5. Observe the apparent first check valve differential pressure (A - B).
6. Install bypass hose between VA and VB. Open VB and bleed

air by loosening hose connection at VA. Tighten hose connec-
tion and close VB.

Push - Print Head (wait) then Push - Start Test

7. Open VA, then slowly open VB (no more than 

1

4

turn). When

relief valve drips, push the “hold” button for 2 seconds.
Record reading (must be 2 psid or more).

Push - Stop Test

8. Close VA and VB.

Test No. 2 - Test No. 2 Check Valve

9. Install bypass hose between VA and TC #4. Open VA, then

bleed air by loosening hose connection at TC #4. Tighten
hose connection. 
Close VA.

Push - Start Test

10. Open VB to reestablish pressure within the “zone”. Close VB.
11. Open VA then TC #4. If relief valve does not drip, record sec-

ond check valve as “closed tight”.

Test No. 3 - Test No. 1 Check Valve

12. Open VB to reestablish first check valve differential pressure.

Close VB. Record pressure differential.

Stop Test (Push Stop Test twice)

13. Close test cocks and remove tester, return assembly to nor-

mal operating condition.

4

Replacement Water Meters for 2

1

2

" - 10" Series 909RPDA, 990RPDA and 992RPDA.

ORDERING

VALVE

CODE

SERIES

SIZE

DESCRIPTION

0835561

909RPDA/990RPDA/992RPDA

2

1

2

" – 10"

D709BA203-GPM-B (registers in gallons)

1203010

909RPDA/990RPDA/992RPDA

2

1

2

" – 10"

D709BB203-CFM-B (registers in cubic feet)

CFM AND GPM Outside Reader Kit

0899022

909RPDA/990RPDA/992RPDA

2

1

2

" – 10"

ROM DC/RP CFM-B

0899023

909RPDA/990RPDA/992RPDA

2

1

2

" – 10"

ROM DC/RP GPM-B

For complete testing information, send for IS-TK-9A or IS-TK-DP/DL.

Watts TK-DP

Water
Meter

Outside

Reader

RPZ

Test 1

RPZ

Test 2

RPZ

Test 3

VA

A

B

VB

VA

B

VB

A

VA

B

VB

A

Содержание 909Series

Страница 1: ...TO THE PRODUCT THE COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRA...

Страница 2: ...t the safe drinking water as per applicable standard Figure 1 Series 909 RELIEF VALVE DISCHARGE RATES ZONE PRESSURE PSIG FLOW RATE GPM Installation Note The flange gasket bolts for the gate valves sho...

Страница 3: ...Test cock 2 3 and 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage G The installation of a Watts air...

Страница 4: ...drips push the hold button for 2 seconds Record reading must be 2 psid or more Push Stop Test 8 Close VA and VB Test No 2 Test No 2 Check Valve 9 Install bypass hose between VA and TC 4 Open VA then...

Страница 5: ...3 RK 909 S 8 200 0887734 RK 909 S 10 250 Kits include Seat Seat O ring Cover O ring Retainer wire and lubricant Total Rubber Parts Kits 0887750 RK 909 RT 21 2 3 65 80 0887751 RK 909 RT 4 100 0887752 R...

Страница 6: ...Bottom plug o ring and lubricant Relief Valve Total 0887235 RK 909 VT 21 2 3 65 80 0887236 RK 909 VT 4 6 100 150 0887237 RK 909 VT 8 10 200 250 0887238 RK 909M1 VT 4 10 100 250 Kits include Adapter o...

Страница 7: ...lve seat or inlet cover check seats Electrically ground the piping system and or electrically isolate the device with plastic pipe immediately upstream and downstream of the device B 6 Valve improperl...

Страница 8: ...web site at www watts com RP IS 909 909RPDA 0829 EDP 1915172 2009 Watts USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada c...

Отзывы: