background image

Figure 2

TYPICAL FLOW RATES

VALVE

AS SIZED BY FLOOR

DRAIN

SIZE

DRAIN MANUFACTURERS

SIZE

in.

mm

in.

mm

2

1

2

"

65

55 gpm

2

50

3"

80

112 gpm

3

65

4"

100

170 gpm

4

100

6", 8", 10" 150,200,250

350 gpm

5

125

Basic Installation Instructions

Series 909

Sizes: 2

1

2

" – 10" (65 – 250mm) 909

High Capacity Relief Series:
Location and Installation Considerations

6. The relief valve module on 2

1

2

" – 10" (65 – 250mm) 909 Series

assemblies may be turned to discharge to the opposite side. To
do so, unbolt the relief valve and turn the relief valve discharge
port to the opposite side. Mount the high pressure hose on the
opposite. This should be done by a licensed journeyman trades-
person, who is recognized by the authority having jurisdiction
and only when space is critical for testing or repair.

7.

ASSEMBLY:

If the backflow preventer is disassembled during

installation, it 

MUST

be reassembled in its 

proper order.

The

gate valve with the test cock is to be mounted on the inlet side
of the backflow preventer. The test cock must be on the inlet
side of the wedge. Please see above. Failure to reassemble cor-
rectly will result in possible water damage due to excessive dis-
charge from the relief port/vent and possible malfunction of
the backflow preventer.

8.

Installation procedures must comply with all state and local
codes and must be completed by a licensed journeyman
tradesperson who is recognized by the authority having juris-
diction.

Please see Page 3 for specific installation procedures.

9. Prior to installation, thoroughly flush all pipe lines to remove any

foreign matter.

10.

START UP at Initial Installation and After Servicing:

The down-

stream shutoff should be closed. Slowly open upstream shutoff
and allow the backflow preventer to fill slowly. Bleed air at each
test cock. When backflow preventer is filled, slowly open the
downstream shutoff and fill the water supply system. This is nec-
essary to avoid dislodging O-rings or causing damage to internal
components.

11.

TEST: 

The 909 Series backflow preventer may be test-

ed by a certified tester at the time of installation in order to
ascertain that the assembly is in full working order and may be
relied upon to protect the safe drinking water as per applicable
standard.

Figure 1 

Series 909 RELIEF VALVE DISCHARGE RATES

ZONE PRESSURE (PSIG)

FLOW RATE (GPM)

Installation Note:

The flange gasket bolts for the
gate valves should be retight-
ened during installation as the
bolts may have loosened due
to storage and shipping.

Relief Valve

First

Check

Second

Check

Second
Shutoff

Valve

Inlet

Shutoff

Valve

2

1

2

" – 3" 909

4" – 10" 909

175

150

125

100

75

50

25

0

0

100 200

300

400

500

600

700

800 900

Watts No. 909

2

1

2

" – 10" (65 – 250mm)

2

1. Backflow preventers must be installed in high-visibility locations in

order to allow for immediate notice of telltale discharge or other
malfunction. This location should also facilitate testing and servic-
ing, and protect against freezing and vandalism.

2. Installing a backflow preventer in a pit or vault is not recom-

mended. However, if this becomes necessary, Watts highly rec-
ommends that a licensed journeyman tradesperson, who is rec-
ognized by the authority having jurisdiction, be consulted to
ensure that 

all local codes and required safety provisions are

met.

An air gap below the relief port must be maintained so as

to avoid flooding and submersion of the assembly, which may
lead to a cross connection. *Please refer to Figure No. 1 for fur-
ther information.

3. A strainer should be installed ahead of the backflow preventer to

protect all internal components from unnecessary fouling.

Caution:

Do not install a strainer ahead of the backflow preventer

on seldom-used, emergency water lines (i.e. fire sprinkler lines).
The strainer mesh could potentially become clogged with debris
present in the water and cause water blockage during an emer-
gency.

4. Normal discharge and nuisance spitting are accommodated by

the use of a Watts air gap fitting and a fabricated indirect waste
line. Floor drains of the same size 

MUST

be provided in case of

excessive discharge. *Please refer to Figure No. 1 and Figure No.
2 for further information.

5. When a 909 Series backflow preventer is installed for dead-end

service applications. (i.e. boiler feed lines, cooling tower makeup
or other equipment with periodic flow requirements), discharge
from the relief vent may occur due to water supply pressure fluc-
tuation during static no-flow conditions. A check valve may be
required ahead of the backflow preventer. *Please see
“Troubleshooting”, Page 7, 

prior to installation.

Содержание 909Series

Страница 1: ...TO THE PRODUCT THE COMPANY MAKES NO OTHER WARRANTIES EXPRESS OR IMPLIED THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRA...

Страница 2: ...t the safe drinking water as per applicable standard Figure 1 Series 909 RELIEF VALVE DISCHARGE RATES ZONE PRESSURE PSIG FLOW RATE GPM Installation Note The flange gasket bolts for the gate valves sho...

Страница 3: ...Test cock 2 3 and 4 When valve is filled open the downstream shutoff slowly and fill the water supply system This is necessary to avoid water hammer or shock damage G The installation of a Watts air...

Страница 4: ...drips push the hold button for 2 seconds Record reading must be 2 psid or more Push Stop Test 8 Close VA and VB Test No 2 Test No 2 Check Valve 9 Install bypass hose between VA and TC 4 Open VA then...

Страница 5: ...3 RK 909 S 8 200 0887734 RK 909 S 10 250 Kits include Seat Seat O ring Cover O ring Retainer wire and lubricant Total Rubber Parts Kits 0887750 RK 909 RT 21 2 3 65 80 0887751 RK 909 RT 4 100 0887752 R...

Страница 6: ...Bottom plug o ring and lubricant Relief Valve Total 0887235 RK 909 VT 21 2 3 65 80 0887236 RK 909 VT 4 6 100 150 0887237 RK 909 VT 8 10 200 250 0887238 RK 909M1 VT 4 10 100 250 Kits include Adapter o...

Страница 7: ...lve seat or inlet cover check seats Electrically ground the piping system and or electrically isolate the device with plastic pipe immediately upstream and downstream of the device B 6 Valve improperl...

Страница 8: ...web site at www watts com RP IS 909 909RPDA 0829 EDP 1915172 2009 Watts USA 815 Chestnut St No Andover MA 01845 6098 www watts com Canada 5435 North Service Rd Burlington ONT L7L 5H7 www wattscanada c...

Отзывы: