Installation, Maintenance, & Repair 

Series 709/LF709/709DCDA

Double Check Valve Assemblies 

Double Check Detector Assemblies

Sizes: 

3

4

" – 10"

RP/IS-709/709DCDA

8" 709 OS&Y shown

Testing

For field testing procedure, reference IS-TK-DL, IS-TK-7, 

IS-TK-9A, IS-TK-99E AND IS-TK-99D at www.watts.com
For other repair kits and service parts, reference PL-RP-BPD at 

www.watts.com
For technical assistance, contact your local Watts 

representative.

NOTICE

For Australia and New Zealand, line strainers should be in-

stalled between the upstream shutoff valve and the inlet of the 

backflow preventer.
Its important that this device be tested periodically in compli-

ance with local codes, but at least once per year or more as 

service conditions warrant. If installed on a fire sprinkler sys-

tem, all mechanical checks, such as alarm checks and back-

flow preventers, should be flow tested and inspected internally 

in accordance with NFPA 13 and NFPA 25.

Installation Instructions

Watts Series 709 and LF709 Double Check Valve may be 

installed in either a vertical or horizontal position - approvals 

may vary by size/model. Refer to relevant ES sheet for com-

plete installation approval details. 
Install valve inline with arrow on valve body pointing in the 

direction of flow.
They should always be installed in an accessible location to 

facilitate testing and servicing.
Pipe lines should be thoroughly flushed to remove foreign 

material before installing the unit. A strainer should be installed 

as shown, ahead of backflow preventers to prevent discs from 

unnecessary fouling.

CAUTION

!

Do not install with strainer when backflow preventer is used on 

seldom-used water lines which are called upon during emer-

gencies, such as fire sprinkler lines, etc.
It is important that Series 709 and LF709 be tested periodi-

cally in compliance with local codes, but at least once a year 

or more often, depending upon system conditions. (Reference 

IS-TK-7 at watts.com).

Clearance Required for Servicing

SIZE

DIMENSION

A

in.

in.

mm

2

1

2

" – 3

10

250

4

15

380

6

15

380

8

23

580

10

25

640

A

Local building or plumbing codes may require modifications to 

the information provided. You are required to consult the local 

building and plumbing codes prior to installation. If this informa-

tion is not consistent with local building or plumbing codes, the 

local codes should be followed.

Need for Periodic Inspection/Maintenance:

 This product 

must be tested periodically in compliance with local codes, but at 

least once per year or more as service conditions warrant. Corro-

sive water conditions, and/or unauthorized adjustments or repair 

could render the product ineffective for the service intended. 

Regular checking and cleaning of the product’s internal compo-

nents helps assure maximum life and proper product function. 

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Содержание 709 Series

Страница 1: ...n material before installing the unit A strainer should be installed as shown ahead of backflow preventers to prevent discs from unnecessary fouling CAUTION Do not install with strainer when backflow preventer is used on seldom used water lines which are called upon during emer gencies such as fire sprinkler lines etc It is important that Series 709 and LF709 be tested periodi cally in compliance ...

Страница 2: ...in parallel should be determined by the engineers judgement based on the operating conditions of a specific installation Above Ground Insulated Enclosure WattsBox Insulated Enclosure Available in Aluminum or Fiberglass For more information reference ES WB at www watts com NOTICE Outdoor Installations In area where freezing conditions do not occur Series 709 and LF709 can be installed outside of a ...

Страница 3: ... wires removed the seat ring can be lifted straight up and removed CAUTION The check valve disc and spring assembly are in compression The spring load is captured by the two spring retainers and the stem The spring retainers are not to be removed for servicing If there is a need to replace the spring spring retainer or stem replace the disc and spring assembly If the disc holder has been damaged b...

Страница 4: ...LITY AND FITNESS FOR A PARTICULAR PURPOSE The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and the Company shall not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does n...

Отзывы: