For indoor installations, it is important that the valve be easily 

accessible to facilitate testing and servicing.

Meter

Strainer

Watts 709S/LF709S

2

1

2

" – 10"

Installation Instructions

Series 709/LF709/709DCDA

Parallel Installations

Two or more Series 709 and LF709 devices may be piped in 

parallel (where approved) to serve a large supply pipe main. This 

type of installation is employed whenever it is vital to maintain a 

continuous supply of water where interruptions for testing and 

servicing would be unacceptable. It also has the advantage of 

providing increased capacity where needed beyond that pro-

vided by a single valve.
For two valve installations the total capacity of the devices 

should equal or exceed that required by the system. Capacity 

table shows the size of the Series 709 and LF709 devices 

required to meet a certain capacity. The quantity of devices used 

in parallel should be determined by the engineers judgement 

based on the operating conditions of a specific installation.

Above Ground Insulated Enclosure

WattsBox Insulated  

Enclosure Available in  

Aluminum or Fiberglass

For more information, reference ES-WB at 

www.watts.com

NOTICE

Outdoor Installations

In area where freezing conditions do not occur, Series 709 and 

LF709 can be installed outside of a building. The most satisfac-

tory installation is above ground and should be installed in this 

manner whenever possible.
It is generally recommended that backflow preventers never be 

placed in pits unless absolutely necessary and then only when 

approved by local codes. In such cases, a modified pit installa-

tion is preferred or an above ground insulated enclosure.

Watts 709/LF709 

2

1

2

" - 10"

Indoor Installations

For indoor installations, it is important that the valve be easily 

accessible to facilitate testing and servicing.

Capacity Required for System

450 GPM

640 GPM

1000 GPM

2000 GPM

3000 GPM

5000 GPM

Two 2

1

2

"

Two 3"

Two 4"

Two 6"

Two 8"

Two 10"

Devices

Devices

Devices

Devices

Devices

Devices

Table shows total capacity provided with dual valve installations of 

various sizes.

Содержание 709 Series

Страница 1: ...n material before installing the unit A strainer should be installed as shown ahead of backflow preventers to prevent discs from unnecessary fouling CAUTION Do not install with strainer when backflow preventer is used on seldom used water lines which are called upon during emer gencies such as fire sprinkler lines etc It is important that Series 709 and LF709 be tested periodi cally in compliance ...

Страница 2: ...in parallel should be determined by the engineers judgement based on the operating conditions of a specific installation Above Ground Insulated Enclosure WattsBox Insulated Enclosure Available in Aluminum or Fiberglass For more information reference ES WB at www watts com NOTICE Outdoor Installations In area where freezing conditions do not occur Series 709 and LF709 can be installed outside of a ...

Страница 3: ... wires removed the seat ring can be lifted straight up and removed CAUTION The check valve disc and spring assembly are in compression The spring load is captured by the two spring retainers and the stem The spring retainers are not to be removed for servicing If there is a need to replace the spring spring retainer or stem replace the disc and spring assembly If the disc holder has been damaged b...

Страница 4: ...LITY AND FITNESS FOR A PARTICULAR PURPOSE The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and the Company shall not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does n...

Отзывы: