Install the Control

7. 

User Interface

Front

Base

Home

Button

ENTER

Home Button

Return to the 

Home Screen  
Press and hold for 3 

seconds to access the 

programming menus.

Touch to go to the 

next setting

Touch to quickly enter

the View menu

Touch to 

adjust settings

Operation

Field

Status Field

Touch to display 

Run Time,

Outdoor & Slab

Temperature

Touch to

Melt or Stop

Touch to turn system 

off while away

8. 

Critical Settings

Item Field

Description

APPLICATIon MoDE

Select the control application mode.

PWM = Hydronic Pulse Width Modulation.

BOIL = Hydronic boiler heats snow melting 

system.

MIX = Hydronic mixing valve or injection 

pump heats snow melting system.

ELEC = Electric snow melt.

090 = Tandem Snow/ Ice Detection

Default = PWM

SnoW / ICE SEnSoR

Select if a Snow / Ice Sensor 090 or Snow 

Sensor 095 is installed.

Default = 090

SLAB SEnSoR

Select if a Slab Sensor 072 is installed to 

measure the slab temperature.
Default = ON

SLAB PRoTECTIon

Select if the slab should be protected from large 

temperature differentials to avoid cracking the 

concrete due to high tensile stress.

Default = ON

The System Menu provides settings on how to configure and operate the mechanical equipment.

Item Field

Description

oUTDooR/BoILER RETURn SEnSoR

Select if the Out/Bret wiring terminal is 

connected to an outdoor sensor or a boiler 

return sensor.

Default = OUT

EConoMELT

EconoMelt allows the user to mechanically 

remove snow then manually start the system 

to melt the thin snow layer or ice.

Default = OFF

tekmarnet

®

 SySTEM PUMP

Select if the system pump located on the 

tekmarNet

®

 System Control should operate 

when the snow melt zone is heating.

Conditions: Application Mode is set to PWM, 

Boil or Mix and Boiler Type is set to CTRL 

(tN4 control).
Default = ON

AUxILIARy RELAy

Select if the auxiliary relay should function 

as system pump or as an alert.

Default = SYS

MAxIMUM MELT TIME

Select to limit the amount of melting run 

time.

Default = 3.0 days