Annual Inspection 

Annual inspection of all water system safety and control valves 

is required and necessary. Regular inspection, testing, and 

cleaning assures maximum life and proper product function. 

NOTICE

 

Shutoff Valves:

 When shutoff valves are removed and reassem-

bly is necessary, the shutoff valve with the test cock is to be 

mounted on the inlet side of the backflow preventer. 

A.  The assembly should always be installed in an accessible location 

to facilitate testing and servicing. 

Check the state and local 

codes to ensure that the backflow preventer is installed in 

compliance, such as the proper height above the ground. 

B.  Watts recommends that a strainer be installed ahead of the 

assembly to protect the internal components from unnecessary 

fouling. 

CAUTION

 

!

 

Do not add a strainer when the backflow preventer is installed on 

seldom-used water lines, such as fire sprinkler lines or other lines 

called upon only during emergencies. 

Start Up:

 The downstream shutoff should be closed. Open the 

upstream shutoff slowly and fill the valve. When the valve is filled, 

open the downstream shutoff slowly and fill the water supply 

system. This is necessary to avoid water hammer or shock 

damage. 

C.  Water discharge from the relief valve should be vented in accor-

dance with code requirements. The relief valve should never be 

solidly piped into a drainage ditch, sewer, or sump. The discharge 

should be terminated approximately 12" above the ground or 

through an air gap piped to a floor drain. 

NOTICE

 

Relief Valve Discharge Rates 

The installation of an air gap with the drain line terminating above 

a floor drain handles any normal discharge or nuisance spitting 

through the relief valve. However, floor drain size may need to be 

designed to prevent water damage caused by a catastrophic 

failure condition. See Figure 4 for maximum relief valve discharge 

rates, size, and capacity of typical floor drains. 

Do not

 reduce the size of the drain line from the air gap fitting. 

Pipe full line size. 

D.  After initial installation, a discharge from the relief valve opening 

may occur due to inadequate initial flushing of pipe lines to 

eliminate dirt and pipe compounds. If flushing does not clear, 

remove the first check valve and clean thoroughly. 

NOTICE

 

Periodic relief valve discharge may occur on dead end service 

applications, such as boiler feed lines or cooling tower makeup 

lines due to fluctuating supply pressure during a static or no flow 

condition. To avoid this discharge, install a spring-loaded rubber 

seated check valve ahead of the backflow assembly to “lock-in

” 

the downstream pressure. 

E.  Backflow preventers should never be placed in pits unless abso-

lutely necessary and then only when and as approved by local 

codes. In such cases, provision should be made to always vent 

above flood level or for a pit drain to ensure an adequate air gap

below the relief port. 

 

F.  The backflow preventers must be inspected periodically for any 

discharge from the relief valve which provides a visual indication 

of need for cleaning or repair of check valves. Also testing for 

proper operation of the device should be made periodically in 

compliance with local codes, but at least once a year or more 

often, depending upon system 

conditions. 
The relief vent discharges water when, during no-flow periods, 

the first check valve is fouled or the inlet pressure to the device 

drops sufficiently due to upstream pressure fluctuations to affect 

the required operating differential between the inlet pressure and 

reduced pressure zone. Otherwise, such relief (spitting) can 

occur when the second check is fouled during emergency 

backflow or resulting from a water hammer condition. (For more 

information, download Troubleshooting Guide S-TSG at 

watts.com.) 

NOTICE

 

Special considerations are necessary when testing assem­

blies installed on Fire Prevention Systems. 
Fire Protection System Installations:

 The National Fire 

Protection Agency (NFPA) Guidelines require a confirming flow 

test be conducted whenever a “main line

 valve such as a back-

flow assembly or the shutoff valves have been operated. Certified 

testers of backflow assemblies must conduct this confirming test. 

Figure 4 

Relief Valve Discharge Rates 

1

2

" – 1" 

45 
40 
35 
30 
25 
20 
15 
10 


0  10  20  30  40  50  60  70  80  90  100 150 

Zone Pressure psi 

Flow Rate gpm 

1

2

3

4

" M2 

1" M2

1

1

4

" – 3" 

350 
300 
250 
200 
150 
100 

50 

0  10  20  30  40  50  60  70  80  90  100  150 

Zone Pressure psi 

Flow Rate gpm

2

1

2

– 3" 

2" M2 

1

1

4

" – 1

1

2

" M2 

TYPICAL FLOW RATES AS SIZED BY FLOOR DRAIN MANUFACTURERS 

2" 55 gpm 

5" 350 gpm 

3" 112 gpm 

6" 450 gpm 

4" 170 gpm 

8" 760 gpm 

Содержание 009 Series

Страница 1: ...f the product s internal components helps assure maximum life and proper product function NOTICE For Australia and New Zealand line strainers should be installed between the upstream shutoff valve and...

Страница 2: ...he assembly should be installed above ground in an insulated enclosure as shown in Figure 2 For more information download the ES WB specification at watts com The assembly must be installed in an acce...

Страница 3: ...lear remove the first check valve and clean thoroughly NOTICE Periodic relief valve discharge may occur on dead end service applications such as boiler feed lines or cooling tower makeup lines due to...

Страница 4: ...lder assembly 5 To reassemble the relief valve press the seat firmly into place in the body center the spring on the seat and insert the cover and relief valve module as a unit straight into the bore...

Страница 5: ...ew assembly from the repair kit O rings should be cleaned or replaced as necessary and lightly greased with the FDA approved silicon grease 5 Reassemble the check valve modules Check modules are insta...

Страница 6: ...n the relief valve of a new installation working with a BMS controller not included 88003057 FP RFK BF BMS CFS BMS Sensor Retrofit Connection Kit Series 009 LF009 LFU009 SS009 U009 Sizes to Includes f...

Страница 7: ...of an existing installation working with cellular communication to send alerts by email message SMS text message or voice call 88003062 FP RFK BF CFS Cellular Sensor Retrofit Connection Kit Series 009...

Страница 8: ...hich is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chem...

Страница 9: ...e du produit et son bon fonctionnement AVIS En Australie et en Nouvelle Z lande les cr pines de conduite doivent tre install es entre le robinet d arr t en amont et l entr e du dispositif de pr ventio...

Страница 10: ...nditions de gel peuvent se produire l ensemble doit tre install au dessus du sol dans une enceinte isol e conform ment la figure 2 Pour plus d informations t l chargez la sp cification ES WB l adresse...

Страница 11: ...iodique de la soupape de d charge peut se produire dans les applications de service aux extr mit s telles que les conduites d alimentation des chaudi res ou les conduites d appoint des tours de refroi...

Страница 12: ...e en place dans le corps centrez le ressort sur le si ge et ins rez le couvercle et le module de soupape de d charge ensemble dans l al sage Appuyer sur le couvercle pour assurer un alignement correct...

Страница 13: ...avec de la graisse au silicone approuv e par la FDA 5 Remonter les modules de clapet antiretour Les modules de clapet sont install s dans le corps de vanne le si ge faisant face l entr e de la vanne...

Страница 14: ...de d charge lors d une nouvelle installation avec un r gulateur BMS non inclus 88003057 FP RFK BF BMS CFS Trousse de connexion de mise niveau de capteur BMS S ries 009 LF009 LFU009 SS009 U009 Tailles...

Страница 15: ...e installation existante fonctionnant avec la communication cellulaire pour envoi d alertes par courriel message texte ou appel vocal 88003062 FP RFK BF CFS Trousse de connexion de mise niveau de capt...

Страница 16: ...ctionne pas correctement les autres co ts r sultant des frais de main d uvre des retards du vandalisme de la n gligence de l encrassement caus par des mat riaux trangers des dommages caus s par des co...

Страница 17: ...ida til y el correcto funcionamiento del producto AVISO Para Australia y Nueva Zelanda se deben instalar coladores de l nea entre la v lvula de cierre de aguas arriba y la entrada del dispositivo de p...

Страница 18: ...producir condiciones de congelaci n el conjunto debe instalarse sobre el piso en un gabinete aislado como se muestra en la figura 2 Para obtener m s informaci n descargue la especificaci n ES WB en wa...

Страница 19: ...de la v lvula de alivio puede ocurrir en aplicaciones de servicio sin salida como l neas de alimentaci n de calderas o l neas de composici n de torres de enfriamiento debido a la fluctuaci n de la pr...

Страница 20: ...e en su lugar en el cuerpo centre el resorte en el asiento e inserte la cubierta y el m dulo de la v lvula de alivio como una unidad recta en el orificio Presione la cubierta hacia abajo para asegurar...

Страница 21: ...la FDA 5 Vuelva a montar los m dulos de la v lvula de retenci n Compruebe que los m dulos est n instalados en el cuerpo de la v lvula con el asiento orientado hacia la entrada de la v lvula Los m dul...

Страница 22: ...rolador BMS no incluido 88003057 FP RFK BF BMS CFS Kit de conexi n de retroadaptaci n del sensor del BMS sistema de gesti n del edificio Serie 009 LF009 LFU009 SS009 U009 Tama os de a 1 27 cm a 1 90 c...

Страница 23: ...alaci n existente vinculada a una comunicaci n celular para enviar alertas por correo electr nico mensaje de texto SMS o llamada de voz 88003062 FP RFK BF CFS Kit de conexi n de retroadaptaci n del se...

Страница 24: ...tamente otros costos resultantes de cargos laborales demoras vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu micos o cualquier...

Отзывы: