Installation 11
Recommended WattNode Models
The following table shows the WattNode models that should be used, depending on the line to
neutral voltage.
Line to Neutral Voltage
WattNode Model
120 Vac
WNC-3Y-208-MB
230 Vac
WNC-3Y-400-MB
277 Vac
WNC-3Y-480-MB
Single-Phase Three-Wire (Mid-Point Neutral)
This configuration is seen in North American residential and commercial service with 240 Vac for
large appliances. The three conductors are a mid-point neutral and two line voltage wires with AC
waveforms 180° out of phase; this results in 120 Vac between either line conductors (phase) and
neutral, and 240 Vac (or sometimes 208 Vac) between the two line conductors (phases).
Figure 3: Single-Phase Three-Wire Connection
Recommended WattNode Models
The following table shows the WattNode models that can be used. If neutral may or may not be
present, you should use the WNC-3D-240-MB (see
Single-Phase Two-Wire without Neutral
below). If neutral is present, it must be connected for accurate measurements. If phase B may
not be present, you should use the WNC-3Y-208-MB (see
Single-Phase Two-Wire with Neutral
above).
Meter Power Source
WattNode Model
N
and
Ø
A
(Neutral and Phase A)
WNC-3Y-208-MB
Ø
A
and
Ø
B
(Phase A and Phase B)
WNC-3D-240-MB
Ground
W
HI
TE
B
L
AC
K
Ø
B CT
Ø
C CT
Ø
A CT
Ø
B
Ø
C
N
Ø
A
Common
B+, D1, RxD+/TxD+
E
IA-
4
8
5
PC or Logger
A−, D0, RxD−/TxD−
Continental Control Systems LLC
Status
Status
Status
X
C
B+
A-
M
O
D
B
U
S
Com
WNC
-
WNC
-
W
ATT
N
ODE
®
M
ODBUS
-
MB
-
MB
Phase A
Neutral
Phase B
WHITE
BLACK
120 VAC
240 VAC
120 VAC
LI
N
E
LO
A
D
Shorting
Jumper
Source
Faces
Current
Transformers
3Y
-
208
3D
-
240