FACTORY PRE-SET OPERATION

Sensor Parameters

    

T-DELAY 

                                       

Time  Delay 

20 minutes

     

Passive Infrared 
Sensitivty

90%

       

W-T

Walk Through

OFF

TROUBLESHOOTING

Loads do not operate as expected.

LEDs don’t light, display 
is off

1.  Check to see that the the sensor is connected to the DLM local Network.

2.  Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. 

If the device does not power up, 24VDC is not present.
• 

Check the high voltage connections to the room controller.

• 

If high voltage connections are good and high voltage is present, recheck DLM local 

Network connections between the sensor and the room controller.

The wrong lights are 
controlled

1.  Configure the sensor to control the desired lights using the Push n’ Learn adjustment 

procedure. 

LEDs turn ON and OFF but 
load doesn’t switch

1.  Make sure device is not in PnL.

2.  Check load connections to room controller.

WARNING:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE 

LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 

– DOING SO MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

      

Load 1

Loads 2-8

or more

**

       

  

 

Plug Load

ON Mode

Operation*

AUTO-ON

MANUAL-ON    

      

if switch is 
used.

AUTO-ON

         

if switch is 
not used.

 

AUTO-ON

Blink Warning

     OFF

     OFF

     OFF

Daylighting

     ON

     OFF

     OFF

*

   Auto-OFF is enabled according to the sensor Time Delay when a 

sensor is bound to the load, regardless of whether the load was turned 
on automatically with occupancy or manually using a switch.

** 

Max 8 loads using LMRC-100 series room controllers.

Mounting plate
back view

European

3.5” 

Octagon

4” Octagon

4” Square

2 Gang

2 Gang

1 Gang

European

3.5”

Octagon

4” Octagon

4” Squar

e

2 Gang

2 Gang

1 Gang

Using a screwdriver, punch out  the

holes for the corresponding junction box.

J-box

Wall

Mounting plate
and base

LMRJ-C8 coupler 
(included, LMRJ-S8 splitter optional)

Occupancy 
Sensor

Snug
Ring

Wall

Snug
Ring
Secure

Snug
Ring
Loose

Screw

through 
wall

MOUNTING 

Mounting plate

Ceiling

Hole

0.825”

(20.9mm) dia.

Stem

Base

Swivel bracket

Occupancy 
Sensor

Ceiling

Mounting plate

Snug

Ring

Loose

Snug

Ring

Secure

Snug
Ring

LMRJ-C8 coupler 
(included, LMRJ-S8 
splitter optional)

WARNING:

 Do Not Install To Cover a Junction Box Having Class 1, 3 or Power and Lighting Circuits.