FACTORY PRE-SET OPERATION
Sensor Parameters
T-DELAY
Time Delay
20 minutes
Passive Infrared
Sensitivty
90%
W-T
Walk Through
OFF
TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t light, display
is off
1. Check to see that the the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location.
If the device does not power up, 24VDC is not present.
•
Check the high voltage connections to the room controller.
•
If high voltage connections are good and high voltage is present, recheck DLM local
Network connections between the sensor and the room controller.
The wrong lights are
controlled
1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment
procedure.
LEDs turn ON and OFF but
load doesn’t switch
1. Make sure device is not in PnL.
2. Check load connections to room controller.
WARNING:
TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE
LMCI-100.
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT
– DOING SO MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Load 1
Loads 2-8
or more
**
Plug Load
ON Mode
Operation*
AUTO-ON
MANUAL-ON
if switch is
used.
AUTO-ON
if switch is
not used.
AUTO-ON
Blink Warning
OFF
OFF
OFF
Daylighting
ON
OFF
OFF
*
Auto-OFF is enabled according to the sensor Time Delay when a
sensor is bound to the load, regardless of whether the load was turned
on automatically with occupancy or manually using a switch.
**
Max 8 loads using LMRC-100 series room controllers.
Mounting plate
back view
European
3.5”
Octagon
4” Octagon
4” Square
2 Gang
2 Gang
1 Gang
European
3.5”
Octagon
4” Octagon
4” Squar
e
2 Gang
2 Gang
1 Gang
Using a screwdriver, punch out the
holes for the corresponding junction box.
J-box
Wall
Mounting plate
and base
LMRJ-C8 coupler
(included, LMRJ-S8 splitter optional)
Occupancy
Sensor
Snug
Ring
Wall
Snug
Ring
Secure
Snug
Ring
Loose
Screw
through
wall
MOUNTING
Mounting plate
Ceiling
Hole
0.825”
(20.9mm) dia.
Stem
Base
Swivel bracket
Occupancy
Sensor
Ceiling
Mounting plate
Snug
Ring
Loose
Snug
Ring
Secure
Snug
Ring
LMRJ-C8 coupler
(included, LMRJ-S8
splitter optional)
WARNING:
Do Not Install To Cover a Junction Box Having Class 1, 3 or Power and Lighting Circuits.
through
ceiling tile
Load
Parameters