![Watt Stopper LC8-120/277 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/watt-stopper/lc8-120-277/lc8-120-277_user-manual_3727227031.webp)
31
User Manual
TROUBLESHOOTING
Problem
What to Check
What to do
The LCD screen is blank
Check that the unit has power,
three red LEDs illuminated on
the main board
LEDs not lit, check for input
power, check circuit breaker.
LEDs are lit, replace main
board
The touch screen does not
control relays
Check that the relay modules
are installed per the instruc-
tions, check that the con-
nectors between the relay
module(s) are firmly seated
together
Properly install relay mod-
ules, firmly seat the connec-
tors
Schedule controls lights at the
wrong time
Check that the time zone is
correctly set. Check that the
date and time are set correctly
Set the proper time zone
Set the proper date and time
Photocell turns lights OFF too
early
Check the aperture setting on
the photocell
Increase the aperture size
on the photocell
Photocell turns lights OFF too
late
Check the aperture setting on
the photocell
Decrease the aperture size
on the photocell
Switch does not control the
lights
Does the corresponding touch
screen INPUT override control
the lights?
Check the wiring of the
switch, replace switch.
Check that the input# is pro-
grammed to control at least
one relay
For further assistance, call Technical Support at 800.879.8585.
Touch Restore Fact. Default
Confirm the action by
touching Yes. To cancel the
action and return to the
menu, touch No
Setup
Restore Fact. Default
Restore Fact.Default
You are about to clear all
Memory to factory default.
Touch the Yes key to clear
all memory and return
to main menu.
[Yes]
[No]