4b. 3-way wiring using two CD-250s:

 

Twist the existing wires together with the wire leads on the CD-250 sensors as 
indicated below. Cap them securely using wire nuts provided. (See Fig. 4b)

•  Connect the green or non-insulated (copper) GROUND wire from the circuit to 

the green wire on the CD-250.

•  Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the 

white wire on the master CD-250.

 

The term “master” designates the CD-250 that connects to the load.

•  Connect the NEUTRAL wire from the circuit in the other wiring box to the white 

wire on the auxiliary CD-250.

•  Connect the power wire from the circuit box (HOT) to the black wire on the 

auxiliary CD-250 and to the TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire from the black wire of the auxiliary CD-250 to 

the black wire of the master CD-250.

•  Connect the lamp power (LOAD) to the red wire on the master CD-250.

•  Cap the red wire on the auxiliary CD-250.

•  Connect the TRAVELER 2 wire coming from the yellow wire of another CD-250 

to the yellow wire of the CD-250 that you are wiring.

AUXILIARY CD-250

MASTER CD-250

Red

Ground

Yellow

Black

White

Red

Ground

Yellow

Black

White

Load

Traveler 1

Traveler 2

Neutral

Hot

120V/60Hz

Neutral

Fig. 4b:  Reference wiring diagram, 3-way using two CD-250s

4c.  Multi-way wiring using one CD-250 and up to four RH-253s:

One CD-250 can be connected with up to 4 RH-253 single pole momentary wall 
switches for multi-way Manual-ON/OFF control of one single load.

 The CD-250 

must be installed in the wiring wall box that connects to the load.

Connect the existing wires to the wire leads on the CD-250 sensor as indicated 
below (See Fig. 4c). Cap them securely using wire nuts provided. 
•  Connect the green or non-insulated (copper) GROUND wire from the circuit to 

the green wire on the CD-250.

•  Connect the NEUTRAL wire from the circuit and from the lamp (LOAD) to the 

white wire on the CD-250.

•  Connect the power wire from the circuit box (HOT) to one terminal on each  

RH-253 single pole momentary wall switch and to the TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire coming from each RH-253 wiring box to the 

black wire of the CD-250.

•  Connect the lamp power (LOAD) to the red wire on the CD-250.

•  Connect the TRAVELER 2 wire to the other side of each RH-253 single pole 

momentary wall switch and to the yellow wire of the CD-250.

Red

Ground

Yellow

Black

White

Load

Traveler 2

Hot

120V/60Hz

Neutral

Traveler 1 (Hot)

RH-253

Ground

RH-253

Ground

Ground

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Traveler 2

Traveler 1

CD-250

Fig. 4c:  Multi-way wiring using one CD-250 and three RH-253s