5. Put the CD-250s (and RH-253s if applicable) into their respective wall boxes.

  Position them with the lens positioned above the ON/OFF/DIM button (lens at 

top, ON/OFF/DIM button at bottom). Secure to the wall box with the screws 
provided.

6. Make any necessary adjustments.

  See the SENSOR ADJUSTMENT section for information.

7.  Install cover plate.

  Install industry standard decorator wall switch cover plate (not included).

8. Restore power to the circuit.

  Turn on the breaker or replace the fuse.

INITIAL POWER-UP DELAY & CALIBRATION

There is an initial one minute warm-up and calibration period the fi rst time 
power is applied to the unit, after a power failure lasting more than 5 minutes 
and after the dimming load is replaced.

Load Calibration: The CD-250 calibrates its dimming range to the load’s wattage 
rating by briefl y dimming the load up and down from its minimum output 
(approx. 10%) to its maximum.

SENSOR ADJUSTMENT

To adjust the CD-250, you use a control located under the ON/OFF/DIM button. 
The wall switch cover plate must be 
removed to gain access to the time 
adjustment dial under the ON/OFF/DIM 
button.

For multi-way operation, the Time 

Delay should be the same in all 

sensors related to the same load.

1.  Firmly grasp the side edges of the 

Lock Bar and gently pull it away from 
the switch face until it clicks. Do NOT 
attempt to pull the Lock Bar off of the 
switch!

2.  Firmly grasp the side edges of the 

ON/OFF/DIM button. Slide the button 
downward approximately 1/2 inch to 
expose the adjustment dials.

Adjusting the Time Delay

Turn the right dial counter-clockwise to 
reduce the amount of time the lights will 
remain on after the last motion detection (minimum = 15 seconds). Turn the 
same dial clockwise to increase this time delay (maximum = 30 minutes). You can 
only select the following values: 15 seconds/5 minutes/15 minutes/30 minutes.

Warning: Do not overturn the Time Delay adjustment dial!

TEST MODE

To test the detection coverage:

1.  Press and hold the ON/OFF/DIM button. After 10 seconds the lighted switch 

turns off. The load turns ON if it was not already ON. The sensor is now in 
a TEST mode that lasts 5 minutes. (You can end the TEST mode sooner by 
pressing the ON/OFF/DIM button for another 10 seconds).

During the TEST mode, the controlled load turns ON for 5 seconds each 

time the sensor that initiated the TEST mode detects occupancy.

2.  Move out of the coverage area or stand very still. The controlled load turns 

OFF after 5 seconds if no motion is detected.

3.  Move into the coverage area for the unit that initiated the TEST mode. The 

controlled load turns ON for 5 seconds each time the sensor detects motion. 
After 5 seconds expire without motion detection, the load turns OFF. The 
controlled load turns ON automatically with the next motion detection and 
stays ON for 5 seconds.

4.  Repeat as necessary to ensure that the desired coverage areas are within 

detection range.

  You can do this test for each CD-250 in your multi-way confi guration. So 

that you can determine the actual coverage area for each multi-way switch 
individually, only the CD-250 that is in TEST mode will control the load.

Lock Bar

Time Delay 
Adjustment
Dial

Slide down
On/Off/Dim
Button

Air Gap Switch

09560r1

Suggested time delays

Bath or Ded room: 30: min.
Half or Stairway: 5-15 min

30

 

   M

in

.

Se
c

.

15

 

Min.

5

Min.

 

1

5

Fig. 5: Sensor Adjustment Controls