CHAPTER 8:
PARAMETER SUMMARY
8-10
Para-
meters
Explanation Settings
Factory
Setting
Actual
Setting
16: CPU WRITE failure
CF2
17: external Base Block stop (b.b)
18: Motor over load
(
oL2)
19: Auto Accel/Decel Failure (CFA)
20: Software/Password Protection
(code)
21: EF1 (External Emergency Stop)
22: PHL (Phase-Loss)
23: cEF (Preliminary count value
attained, EF active)
24:Lc (Low-current)
25:AnLEr (Analog feedback signal
error)
06-11 Fourth Most Recent
Fault Record
26:PGErr (PG feedback signal error)
06-12 Low-Current Detection Level 00 to 100% (00: Disabled)
00
06-13 Low-Current Detection Time
0.1~ 3600.0 Sec
10.0
00: Warn and keep operating
01: Warn and ramp to stop
02: Warn and coast to stop
06-14 Low-Current Detection
Treatment
03: Warn, after coast to stop, restart
(delay 06-15 setting time)
0
06-15 Low-Current Detection Restart
Delay Time
1~600 Min.
10
220VDC to 300VDC*
06-16 User-Defined Low-Voltage
Detection Level
0: Disabled
00
06-17 User-Defined Low-Voltage
Detection Time
0.1~ 3600.0 Sec
0.5
06-18 Reserved – Do Not Change!