10
Stall Prevention
12
xxx0 : Stall prevention during accel. Enable
xxx1 : Stall prevention during accel. disable
xx0x : Stall prevention during decel. enable
xx1x : Stall prevention during decel. disable
x0xx : Stall prevention during running enable
x1xx : Stall prevention during running disable
0xxx : Stall prevention decel. time set by Fn 02
1xxx : Stall prevention decel. time set by Fn 15
0000
13
Stall prevention starting level
during accel
1% 30-200%
110%
14
Stall prevention level during
running
1% 30-200%
160%
15
Decel time during stall prevention 0.1 sec
0.1-3600 sec
3 sec
*1
Direct start &
Reset &
numbers of input
signal scanning
16
xxx0 : Direct start enable when remote RUN command ON
xxx1 : Direct start disable when remote RUN command ON
xx0x : Reset effective only if remote RUN command OFF
xx1x : Reset effective disregard of remote RUN command condition
00xx : TM2 will scan 10 times
01xx : Tm2 will scan 5 times
10xx : Tm2 will scan 3 times
11xx : TM2 will scan 1 time
0000
Multi-Speed
17
Multi-speed 1
0.01 Hz
0-400 Hz
5.00 Hz
*1
18
Multi-speed 2
0.01 Hz
0-400 Hz
10.00 Hz
*1
19
Multi-speed 3
0.01 Hz
0-400 Hz
20.00 Hz
*1
20
Multi-speed 4
0.01 Hz
0-400 Hz
30.00 Hz
*1
21
Multi-speed 5
0.01 Hz
0-400 Hz
40.00 Hz
*1
22
Multi-speed 6
0.01 Hz
0-400 Hz
50.00Hz
*1
23
Multi-speed 7
0.01 Hz
0-400 Hz
60.00 Hz
*1
Jog freq.
24
Jog freq. reference
0.01 Hz
0-400 Hz
2.00 Hz
*1
Master freq.
25
Master freq. reference from digital
operator
0.01 Hz
0-400 Hz
5.00 Hz
*1
Analog input
26
Freq. reference
0.01 Hz
0.0-400 Hz
0 Hz
*1
freq.
27
Voltage reference ratio 1
0.1 %
0-100.0%
0%
*1
command
28
Voltage reference ratio 2
0.1 %
0-999.9%
100%
*1
29
Positive / Negative direction
1
0 : Positive
1 : Negative
0 *1
Power voltage
30
Voltage of power supply
0.1 V
200 - 480 V
*3